Air conditioner | Edition: 10070808 | |
|
|
|
temperature, sleep state, flap state.
c. Cancellation of function: Pressing the SLEEP button on the remote control unit for 10 times until hearing 2 sounds from the buzzer on the panel.
3.2.11Trial run function
When the air conditioner is in OFF state, press the emergency switch for 5 seconds till hearing 2 sounds of click from the buzzer, then the air conditioner will turn to the trial run state. The unit will run in the refrigerating mode and the indoor fan will run in high wind speed mode.
3.2.12Emergency running mode
When the air conditioner is in
a.Tr≥23℃, running refrigerating mode, Ts = 26℃;
b.Tr<23℃, running heating mode, Ts = 23℃.
3.2.13Temperature compensation.
There is the function of automatic temperature compensation when heating, with heating temperature setting = Ts(remote setting) + 4℃.
3.2.14Sleeping function
a. After setting the sleeping function, the refrigerating mode and dehumidification mode will run as per the following rules:
T(℃)
Ts+2
Ts+1 1 hours
6hours
1 hour
Ts SleepOFF t(hour)
b. After setting the sleeping function, the heating mode will run as per the following rules:
T(℃)
Ts
1 hour
3hours
3hours
As shown in the above diagram, after running for 1 hour under refrigerating mode and dehumidification mode, the setting temperature will increase 1℃; after
- 8 -