MHC36 AND MHR36 INSTALLATION INSTRUCTIONS
2.Frame the Fireplace
The MHR36 and MHC36 fireplaces will fit a framed opening of
Figure 5 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All required clearances to combustibles around the fireplace must be adhered to. Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney section.
Note: The top header may be positioned on the hemmed seam across the top of the fireplace assembly.
Figure 5 - Framing the Fireplace
CLEARANCES!
A minimum 1 in. air clearance must be maintained at the back and sides of the fireplace assembly except at the nail- ing flange where the clearance is 1/2 in. Chimney sections at any level require a 2 in. minimum air space clearance be- tween the framing and chimney section.
WARNING!
Do not apply combustible finishing materials over any part of the black face of this fireplace or a structure fire may result. The black metal fireplace front may only be covered with noncombustible materials such as ce- ramic tile, brick, or stone. Do not cover or block any cooling air slots. Do not cover any portion of the opening to the fireplace that would prevent the installation of an authorized glass door.
10 | 31072 Rev G | 08/04 |