Heat & Glo LifeStyle EXCLAIM-42H-C, EXCLAIM-42T-C owner manual A. Chimney Requirements, Fire Risk

Models: EXCLAIM-42H-C EXCLAIM-42T-C

1 52
Download 52 pages 11.65 Kb
Page 20
Image 20
A. Chimney Requirements

A. Chimney Requirements

Vertical distances are measured from the base of the fire- place as shown in Figure 5.2.

 

ft

m

• Minimum overall straight height

18

5.5

• Minimum height with offset/return

18.5

5.6

• Maximum height

90

27.4

• Maximum chimney length between an offset and

20

6

return

 

 

• Maximum distance between chimney stabilizers

35

10.7

• Double offset/return minimum height

24

7.3

• Maximum unsupported chimney length between the

6

1.8

offset and return

 

 

• Maximum straight unsupported chimney height

35

10.7

above the fireplace

 

 

• Maximum unsupported chimney above roof

6

1.8

To determine the chimney components needed to complete your particular installation, follow the steps below:

Determine the total vertical height of the fireplace installation. This dimension is measured from the base of the fireplace assembly to the point where the smoke exits the termination cap.

Subtract the effective height of the fireplace assembly from the overall height of the fireplace installation (measured from the base of the fireplace to the bottom of the termination cap).

Refer to Table 5.1 to determine what components must be selected to complete the fireplace installation.

Determine the number of ceiling firestops, stabilizers, roof flashing, etc. required to complete the fireplace installation.

Note: A maximum of two pairs of offsets and returns may be used.

Table 5.1 WARNING

Fire Risk

Must maintain 2 in. (51 mm) air clearance to insulation and other combustible materials.

Table 5.1

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

 

 

 

SL4

4-3/4

121

Ceiling Firestops

 

 

 

FS538

0

0

 

FS540

0

0

Offsets/Returns

 

 

 

SL430

14-1/2

368

Roof Flashing

 

 

6 ft (1.8 m) max. unsupported run

20 ft (6 m) max. pipe between an offset & return

Ceiling Firestop

71-3/4 in.

(1822 mm)

Effective Height

(bottom of fireplace

to top of starter collar)

6 ft (1.8 m) max. unsupported chimney Manual background above roof

35 ft (10.7 m) max. straight unsupported chimney height

18.5ft (5.6 m) min. height/single offset-return 24 ft. (7.3 m) min. height/double offset-return

90 ft (27.4 m) max. height

 

RF570

0

0

 

 

 

 

 

RF571

0

0

Chimney Sections*

 

 

 

SL406

4-3/4

121

 

SL412

10-3/4

273

 

SL418

16-3/4

425

 

 

 

 

 

SL436

34-3/4

883

 

SL448

46-3/4

1187

* Dimensions reflect effective height.

 

 

Figure 5.2 Chimney Requirements

Manual background CAUTION

Do NOT connect this fireplace to a chimney flue servicing another appliance.

Do NOT connect to any air distribution duct or system.

20

Heat & Glo • EXCLAIM-42C4013-094 Rev I • 10/06