35
Service Record

Date of Start-up

Location Address

CONDENSING UNIT
MODEL #
SERIAL #
COOLER UNIT
MODEL #
SERIAL #
FREEZER UNIT
MODEL #
SERIAL #

ELECTRICAL

Check Primary Supply voltage.
If 208 V, change transformer wiring in the
Cooler and Freezer to the 208 V tap
YES
Check Compressor Amps for COOLER and
FREEZER compressors. Should match
nameplate.
YES NO

PIPING

•Is suction line trapped at the Cooler?
YES NO
•Is suction line trapped at the Freezer?
YES NO

DRAIN LINES

•Are drain lines sloped properly?
YES NO
•Is drain line trapped outside the Cooler?
YES NO
•Is drain line trapped outside the Freezer?
YES NO
•Is heat tape wrapped along entire length of
the drain line in the Freezer?
YES NO
•Is heat tape plugged in and heating the drain
line?
YES NO

INSULATION

•Are Liquid lines fully insulated?
YES NO
•Are Suction lines fully insulated?
YES NO

SETTINGS

Check Beacon II board settings for the
following:
FREEZER
Refrigerant Type R404A
Box Setpoint Temp. -10°F.
Superheat 8°F.
No. of Defrost/Day 4
Defrost End Temp. 65°F.
COOLER
Refrigerant Type R22
Box Setpoint Temp. 35°F.
Superheat 8°F.
No. of Defrost/Day 2
Defrost End Temp. 50°F.

SYSTEM CHECKS

Check Compressor Superheat for the
COOLER (Should be between 20°F. & 30°F.)
YES NO
Check Compressor Superheat for the
FREEZER (Should be between 20°F. & 30°F. )
YES NO
Force unit into a Defrost Check heater amps.
Should match nameplate amps.
YES NO
Check LPS Time Delay Relays. Should be
set at 1 minute for both the COOLER and
FREEZER.
YES NO
Check Low Pressure Switch on FREEZER. Should
be set at 0 psig Cut-out/10 psig Cut-in.
YES NO
•Did FREEZER and COOLER cycle off on LPS at
Setpoint Temperature?
YES NO
•Is the sight glass free of bubbles?
YES NO
•Are the COOLER and FREEZER fans at proper
speeds?
YES NO
Check system for refrigerant leaks. Are there any
leaks on the COOLER, FREEZER, CONDENSING
UNIT or INTERCONNECTING PIPING?
YES NO
Check system piping for unusual vibration or noise.
Is there any unusual vibration or noise on the
COOLER, FREEZER, CONDENSING UNIT or
INTERCONNECTING PIPING?
YES NO
•Start the FREEZER only. Does the compressor
start and evaporator fans run for this FREEZER?
YES NO