25
Beacon II Controller
System DefaultsFigure 15. Control Sensor And Piping Table 5. System Defaults

Parameters Code Air Electric

Refrigerant
rEF
R22 R404A
Box Temperature
bot
35°F-10°F
Superheat
SUP
8°F8°F
Slave Evaporator
SLA
No No
No. of Defrosts Per Day
dFn
24
Defrost Fail-Safe Time
dFF
40 min. 30 min.
Defrost End Temperature
dFt
45°F60°F
Defrost Delay Start Time
dFS
0 hrs. 0 hrs.
Alarm High Temperature
ALH
50°F5°F
Alarm Low Temperature
ALL
30°F-15°F
Alarm Time
ALt
60 min. 60 min.
Temperature Units
F-C
°F°F