Heatcraft Refrigeration Products LAG, LAL, LAH manual Physical Data, Standard Nozzle Selection

Models: LAL LAG LAH

1 8
Download 8 pages 1010 b
Page 7
Image 7
Physical Data

Physical Data

Model LAH/LAL/LAG Air/Electric/Hot Gas Defrost

Model

Connections OD (in.)

Approx. Net Weight

Inlet

Suction

Hot Gas

lbs.

kg

 

LA*070

1/2

7/8

1/2

178

81

LA*090

1/2

7/8

1/2

189

86

LA*120

1/2

7/8

1/2

262

119

LA*130

1/2

7/8

1/2

264

120

LA*160

1/2

1-1/8

1/2

280

127

LA*170

1/2

1-1/8

1/2

285

129

LA*190

1/2

1-1/8

1/2

298

135

LA*220

1/2

1-1/8

1/2

366

166

LA*270

1/2

1-3/8

5/8

405

184

7/8" inlet on hot gas defrost models

LAH= Air Defrost

LAL = Electric Defrost

LAG = Hot Gas Defrost

Standard Nozzle Selection

Model LAH Air Defrost

 

 

Distributor Type

 

No. of

R-404A

R-22

Model

 

OD

Length

 

Circuits

Nozzle*

Nozzle

 

in.

 

cm

in.

cm

 

 

 

 

 

LAH070

3/16

 

0.5

24

 

61

2

L-1/2

L-1/3

LAH090

3/16

 

0.5

24

 

61

2

L-3/4

L-1/2

LAH120

3/16

 

0.5

24

 

61

4

L-1

L-1/2

LAH130

3/16

 

0.5

24

 

61

4

L-1

L-3/4

LAH160

3/16

 

0.5

24

 

61

4

L-1

L-3/4

LAH170

3/16

 

0.5

24

 

61

6

L-1-1/2

L-3/4

LAH190

3/16

 

0.5

24

 

61

4

L-1-1/2

L-1

LAH220

3/16

 

0.5

24

 

61

6

L-2

L-1

LAH270

3/16

 

0.5

30

 

76

12

L-2

L-1-1/2

Model LAL Electric Defrost

 

 

Distributor Type

 

No. of

R-404A

R-22

Model

 

OD

Length

 

Circuits

Nozzle*

Nozzle

 

in.

 

cm

in.

cm

 

 

 

 

 

LAL070

3/16

 

0.5

24

 

61

2

L-3/4

L-1/2

LAL090

3/16

 

0.5

24

 

61

2

L-1

L-3/4

LAL120

3/16

 

0.5

24

 

61

4

L-1-1/2

L-3/4

LAL130

3/16

 

0.5

24

 

61

4

L-1-1/2

L-3/4

LAL160

3/16

 

0.5

24

 

61

4

L-2

L-1

LAL170

3/16

 

0.5

24

 

61

6

L-2

L-1

LAL190

3/16

 

0.5

24

 

61

4

L-2-1/2

L-1-1/2

LAL220

3/16

 

0.5

24

 

61

6

L-3

L-1-1/2

LAL270

3/16

 

0.5

30

 

76

12

L-3

L-2

Model LAG Hot Gas Defrost

 

 

Distributor Type

 

No. of

R-404A

R-22

Model

 

OD

Length

 

Circuits

Nozzle*

Nozzle

 

in.

 

cm

in.

cm

 

 

 

 

 

LAG070

1/4

 

0.6

24

 

61

2

L-3/4

L-1/2

LAG090

1/4

 

0.6

24

 

61

2

L-1

L-3/4

LAG120

1/4

 

0.6

24

 

61

4

L-1-1/2

L-3/4

LAG130

1/4

 

0.6

24

 

61

4

L-1-1/2

L-3/4

LAG160

1/4

 

0.6

24

 

61

4

L-2

L-1

LAG170

1/4

 

0.6

24

 

61

6

L-2

L-1

LAG190

1/4

 

0.6

24

 

61

4

L-2-1/2

L-1-1/2

LAG220

1/4

 

0.6

24

 

61

6

L-3

L-1-1/2

LAG270

1/4

 

0.6

30

 

76

12

E-3

E-2

*also suitable for R-507, R-502, R-134A, R-401A, R-402A

NOTE: Nozzles sized for 90-100˚F liquid temp. at expansion valve. Refer to I&O manual if liquid temp. is not 90-100˚F.

Note: Refrigeration system will not perform properly without correct nozzle!

Page 7
Image 7
Heatcraft Refrigeration Products LAG, LAL manual Physical Data, Standard Nozzle Selection, Model LAH Air Defrost