C. Sidewalls/Surrounds
•Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from fireplace opening.
•Mantle leg, surround, stub wall, whether combustible or
Note: Grid depicts 1 inch squares.
FLUSH FRONT
BRICK | 4 in. | |
[102 mm] | ||
FRONT | ||
|
22 3/8 in.
[568 mm]
50° | angle |
|
18 1/2 in.
[470 mm]
24 in. [610 mm]
42in.
[1067 mm]
(1343 mm)
39° | angle |
|
24 in. [610 mm]
19 3/4 in.
[500 mm]
Figure 6.3 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)
D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
•Observe all required air space clearances to combustible materials as shown in Figure 6.2.
2 in. (51 mm) min. air space clearance
from chimney.
Framing must be extended straight up, all the way to the ceiling.
The fireplace header cannot be positioned until after the fireplace assembly is in place.
Header MUST NOT be notched!
C
D A
D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be reduced as long as minimum clearances are met.
B | D |
Model # |
| A | B * | C ** | D |
BIR42 | in. | 53 7/8 | 28 3/8 | 74 1/2 | 12 |
| mm | 1368 | 721 | 1892 | 305 |
*If interior of chase will be drywalled, add the thickness to this meaurement.
**Adjust header height for raised floor under fireplace.
Figure 6.4 Framing the Fireplace
20 | Heatilator • Birmingham BIR42 • |