5-6. Selecting A Location And Connecting Input Power

18 in (457 mm) of space for airflow

YDo not move or operate unit where it could tip.

=GND/PE Earth Ground

1

6

9

5

7

 

 

 

 

L1

 

2

L2

 

 

 

 

 

 

 

 

3

4

1 10

8

 

L2

L1

 

230 VAC, 1

YSpecial installation may be required where gasoline or volatile liquids are present − see NEC Article 511 or CEC Section 20.

YInstallation must meet all Na- tional and Local Codes − have only qualified persons make this installation.

YDisconnect and lockout/tag- out input power before con- necting input conductors from unit.

YAlways connect green or green/yellow conductor to supply grounding terminal

first, and never to a line ter- minal.

1 Rating Label

Supply correct input power.

2Black And White Input Conductor (L1 And L2)

3Green Or Green/Yellow Grounding Conductor

4Input Power Cord.

5Disconnect Device (switch shown in the OFF position)

6Disconnect Device Grounding Terminal

7Disconnect Device Line Terminals

Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.

Connect input conductors L1 and L2 to disconnect device line terminals.

8Receptacle (NEMA 6-50R) Connect receptacle as shown.

9Over-Current Protection

Select type and size of over-current protection using Section 5-7(fused disconnect switch shown).

Close and secure door on disconnect device. Remove lockout/tagout device, and place switch in the On position.

10Plug (NEMA 6-50P) Connect plug to receptacle.

ssb2.2* 1/94 − 804 687-A

OM-227 978 Page 14

Page 18
Image 18
Hobart Welding Products 210 manual Selecting a Location And Connecting Input Power, First, and never to a line ter- minal