Figure 2 UDC3500 terminal connections

If you have:

MDI-compliant hub with straight-through cable or

PC with crossover cable

then make these connections:

 

UDC Terminal

UDC Signal Name

Wire Color

RJ45 Socket Pin #

Hub/PC Signal Name

 

Position 4

Shield

Black/Bare

Shield

Shield

 

Position 24

RX-

Orange

6

TX-

 

Position 25

RX+

White/Orange

3

TX+

 

Position 26

TX-

Brown

2

RX-

 

Position 27

TX+

White/Brown

1

RX+

 

 

 

2

If you have PC with straight-through cable then make these connections:

 

 

UDC Terminal

UDC Signal Name

Wire Color

RJ45 Socket Pin #

PC Signal Name

 

Position 4

Shield

Black/Bare

Shield

Shield

 

Position 24

RX-

Brown

2

TX-

 

Position 25

RX+

White/Brown

1

TX+

 

Position 26

TX-

Orange

6

RX-

 

Position 27

TX+

White/Orange

3

RX+

 

 

3

Secure cable to controller by attaching tie wraps through the holes in the controller flange.

 

 

 

 

 

 

Warranty/Remedy

Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.

While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application

Honeywell Process Solutions

 

Industrial Measurement and Control

 

512 Virginia Drive

 

Fort Washington, PA 19034

www.honeywell.com\imc

Page 2
Image 2
Honeywell 2500, 3200 manual UDC3500 procedure, L2/N, Ethernet Adaptor Kit, Tie Wraps, Warranty/Remedy