ADJUSTMENTS AND CHECKOUT

and associated flame safeguard controls.

Move the detector and sight pipe around to sight the flame at various positions and angles. Try to get a maximum steady meter reading. The signal must be above the minimum acceptable current/voltage listed in Table 6.

Measure the fIame signal for the pilot alone, the main burner flame alone, and both together (unless monitoring only the pilot flame when using an intermittent pilot, or only themain burner flame when using direct spark ignition). Also measure the flame signal at high and low firing rates and while modulating in between (as applicable). With the detec- tor in its final position, all required fhune signals must be steady and as specified in Table 6. If you cannot obtain the proper signals, refer to the Troubleshooting section.

Fig. 12-Measuring microamp flame Signal.

PLUG-IN FLAME

SIGNAL AMPLIFIER

I

W136A

SELECTOR

196146 METER

TEST METER

SWITCH,

CONNECTOR

 

 

RED CONNECTOR

CK CONNECTOR

M E T E R ‘

LEAD

El 208

Fig. K&Measuring BCS 7700 Flame Safeguard Control flame signal voltage.

\PROBES

\ ECS 7700 CHASSIS MODULE FOOTMOUNT

E2512A

Fig. 14-Measuring 7800 SERIES Flame Safeguard Control flame signal voltage.

TABLE 6-FLAME SIGNAL

 

 

 

 

 

1

Minimum 1 Maximum 1 Minimum 1

Maximum

 

 

Flame

 

 

 

 

Acceptable

Expected

Acceptable

Expected

 

 

Signal

 

 

 

 

Steady Current

Current

Steady Voltage

Voltage

 

 

Amplifier

 

 

Flame Safeguard Control

 

(microamp)

(microamp)

(Vb)

(Vdc)

 

 

R7248A

 

 

BC7OOOL; R4075C,D,E;

 

2.25

5.0

 

 

 

 

 

 

 

R4138CD; R414OG;L;M

 

 

 

 

 

 

 

R7248B

 

 

BC7OOOL; R4075C,D,B;

 

3.5

5.0

 

 

 

AMF’LI-CHECK~

 

R4138CD; R414OGL.M

 

 

 

 

 

 

 

R7258A

 

 

R4150

 

4.0

5.5

 

 

 

 

R7748B

 

 

BCS 7700

 

 

 

2.2

4.98

 

AMPLI-CHECKTM

 

 

 

 

 

 

 

 

 

 

R7848A

 

 

RM78OOE,G,L,M; RM7823A;

 

 

 

1.25

5.0

 

 

 

 

 

RM7838A,B; RM784OE,G,L,M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

RM7885A: RM789OA,B;

I

 

 

I

 

 

 

 

 

 

RM7895A;B,C,D

 

 

 

 

 

 

 

R7848B

 

 

RM78OOE,G,L,M; RM7823A;

 

 

 

1.25

5.0

 

AMPLI-CHECX=

 

RM7838AB; RM784OE,G,L,M;

 

 

 

 

 

 

 

 

 

 

RM7885A; RM789OA,B;

 

 

 

 

 

 

 

 

 

 

RM7895A,B,C,D

 

 

 

 

 

 

1160-2306-5