F300 ELECTRONIC AIR CLEANER
68-0240EF-5 10
Reassemble Air Cleaner!Insert the electronic cells with the gray contact board toward
the power supply and the airflow arrow pointing
downstream. If the cell does not slide easily into the cabinet,
check the orientation of the cell key.
!Insert the metal mesh prefilters on the upstream side of the
cabinet in the guide provided.
!Insert the media postfilters (on select models) on the
downstream side of the cabinet in the guide provided.
!Replace the access door. Insert the tab on the bottom of the
door into the slot in the cabinet, then swing it closed and
press into place. The door must be firmly in place or the air
cleaner will not operate.
Complete WiringWARNING
Electric Shock Hazard.
Can cause personal injury.
Do not use an extension cord.
• Assure all wiring complies with local codes and ordinances.
• The line voltage power source must match the voltage and
frequency printed on the label inside the access door.
• When the System fan comes on, the Air Flow Switch (AFS)
senses the negative pressure in the duct and turns on the
power supply. If power to the air cleaner is controlled by
another switch, the AFS can be disabled by disconnecting
the AFS plug J3 and cutting the J8 jumper on the power
supply. See Fig. 10.
!Plug the electronic air cleaner directly into the correct
voltage and frequency outlet. See Fig. 10 for internal
schematic. The air cleaner operates correctly with any fan
when wired with conduit or plugged in.
NOTE: To reduce the risk of electric shock, this product has a
grounding type plug that has a third (grounding) pin.
This plug only fits into a grounding type power outlet.
If the plug does not fit into the outlet, contact a quali-
fied electrician to install the proper outlet. Do not
change the plug in any way.
!Alternatively, the electronic air cleaner can be wired with
conduit.
Fig. 10. Internal schematic for electronic air cleaner.
P3
P4
P1
P2
J3
BLACK
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
ORANGE
GRAY
VIOLET
BLACK
1 INTERLOCK SWITCH.
2 SHORTING BAR FOR OZONE REDUCTION.
3 AIRFLOW SWITCH DISABLE JUMPER, J8.
AIRFLOW SWITCH PLUG, J3.
4 NEON LIGHT.
5 OPTIONAL W8600F AIR CLEANER MONITOR. M23413
POWER
SUPPLY
2
4
BLACK
BLACK BLACK
BROWN
BLACK
BLACK
WHITE
GREEN
1
3
J4
J5
J1
BLACK
RED
TEST
BUTTON
CONTACT
BOARD
RED IONIZER
BLACK COLLECTOR
5
J8