![](/images/backgrounds/250070/bg5.png)
l404A
D
Fl604A
l
MINSTALLATION
Installation
WHENINSTALLINGTIllSPRODUCT1
Readthese instructions
carefullyFailureto
followthem
coulddamage
the
product
or
cause
a
hazardouscondition2
Checkthe
ratingsgivenin
the
instructions
and
on
the
prod
ct
to
make
sure
the
product
is
suitablefor
yourapplication
3
Installermust
be
a
tramedexpenencedflame
safeguardcontroltechnician4
After
installationis
completecheck
out
product
operation
as
providedin
these
instructions
ffiCAUTION
1
Disconnectpower
supplybefore
beginningin
stallation
to
prevent
possibleequipmentdam
age
or
electrical
shock
2
When
using
the
controller
with
a
compressorinstall
a
dampeningdevice
such
as
aneed1e
valveheader
or
surge
tank
to
dampen pulsationsthat
can
damage
the
controller
or
reduceits
life
IMPORTANT1
Locate
the
controller
where
the
ambient
temperature
will
not
exceed
1500F
660C2
Use
pipe
compoundsparinglyto
avoid
cloggingthe
hole
in
the
pipe
or
diaphragmfitting
3
Do
not
tightenthe
controller
by
hand
by
holdingthe
case
4Accuratelylevel
the
controller
forproper
operation
LOCATIONAND
MOUNTINGNOTE
For
most
accurate
operation
add
supplementalheat
to
installations
where
the
temperature
falls
belowminus
200P
minus290CNever
locate
the
controller
where
the
temperatUrefalls
below minus
350P
minus
370Cbe
cause
mercury
in
the
switchfreezes
at
this
temperature
When
used
with
steam
boilers
always
mount
the
con
troller
above
the
water
line in
the
boiler
A
steam
trap
siphonloopmust
always
beconnected
between
the
con
troller
andthe
boiler
Fig 2
to
prevent
boiler
scale and
corrosive
vapors
from
attackingthe
diaphragmThe
loop
on
the
steam
trap
must
always
be
perpendicularto
the
face
of
the
controller
If
the
loop
is
parallelto
the
controller
expansionor
contraction
of
the
loop
tipsthe
controller
and
causes
the
switch
to
operateinaccuratelyThe
controller
can
be
mounted
1
alongsidethe
pres
sure
gauge
2
in
a
fitting
on
the
boiler
providedby
e
manufacturer
3
at
a
remote
location
in
caseof
excesSIve
vibration
or
4
in
a
special
mountingon
a
low
water
cutoff
Fig
2
Rlghtandwrong
mountingof
a
steam
trap
siphon
loopwith
approximatedimen
sions
inin
mm
1
4
IN
BLACK
IRON
PIPE
WITH
1
4
18
NPT
EXTERNAL
TRHEADSON
BOTHENDS
BEf
lD
THE
STEAM
TRAP
SIPHON
LOOP
TO
LEVEL
THE
CONTROLLER
M8934
Make
all
pipe
connections
in
accordance
with
approvedstandards
Use
onlya
small
amount
of
pipe
compoundto
seal
the
connectionjointsExcess
pipe
compoundcan
clogthe
small
hole
in
the
fitting
and
prevent
the
controller
from
operating
properly
Toavoid
leaks
and
damage
to
the
case
use
a
parallelJawwrenchon
the
controller
s
hexagonalfitting
Donot
tigten
the
controller
by
hand
by
holdingthe
case
LeveUngA
controller
with
a
mercury
switch
must
be
accuratelyleveled
for
proper
operation
It
is
level
when
the
leveling
indicator
Fig
11
hangsfreelywith
its
pointerdirectlyover
the
index
mark
inside
the
back
of
the
case
Level
the
controller
bycarefu11y
bendingthe
steam
trap
siphon
loop
MountingAlongsidea
Pressure
GaugeTo
mount
the
controller
alongsidea
pressure
gauge
Fig
2
remove
the
gauge
In
its
placeinstall
a
steam
ap
siphon
loop
with
a
tee
on
topUsing
elbows
and
pIpe
nipplesmoUnt
the
controller
and
pressure gau
e
on
the
ends
of
the
teeLevel
the
controller
after
installattOn
I
11