Honeywell N-ANN-RLY specifications Alarm 75 mA Standby 15 mA, UL S635, N-Ann-Rly, Relay Module

Models: N-ANN-RLY

1 2
Download 2 pages 23.33 Kb
Page 1
Image 1
N-ANN-RLY

N-ANN-RLY

Relay Module

General

The N-ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP (Fire Alarm Control Panel). The N-ANN-RLY module may be mounted inside the FACP main circuit board chassis or in the battery area of the enclosure using optional mounting bracket P/N: ANN-MBRLY. Reference Installation Instructions document #53318.

The N-ANN-RLY and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication for- mat. An additional two wires are used for 24-volt DC power. A single four-conductor unshielded cable may be used for both power and data communications.

Up to eight ANN-BUS devices may be connected to the ANN- BUS of each FACP.

Features

N-ANN-RLY connects to the ANN-BUS terminal on the FACP and requires minimal programming.

Provides 10 programmable Form-C relays.

Ten Form-C relays can be programmed for various func- tions; Alarm, Trouble, Supervisory, AC Loss, Waterflow Delay, Input Zones and Silenceable Alarm.

Compatible with the FireWarden 50, SFP-5UD, RP-2001, RP-2002 and SFP-10UD.

May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC).

Up to eight ANN-BUS devices may be connected to the ANN-BUS of each FACP.

Listed to UL Standard 864, 9th Edition.

Specifications

Maximum ANN-BUS Voltage: 24 VDC

Maximum Current:

– Alarm: 75 mA Standby: 15 mA

Ambient Temperature: 32ºF to 120ºF (0ºC to 49ºC)

Relative Humidity: 93% ± 2% RH (noncondensing) at 32ºC

± 2ºC (90ºF ± 3ºF)

For use indoors in a dry location

Connections to FACP are power-limited and supervised.

Relay Contact Ratings: 2 Amps @ 30VDC (Resistive) 0.5 Amps @ 30VAC (Resistive)

Agency Listings and Approvals

The listings and approvals below apply to the N-ANN-RLY. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status.

UL: S635

CSFM:7165-0028:245; 7165-0028:246

MEA: 333-07-E

DN-7107:AK-20

Annunciators

52431cov.jpg

The ANN-BUS

POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY

ANN-BUS devices can be powered by an auxiliary power sup- ply when available panel power is exceeded. See FACP man- ual for information.

ANN-BUS DEVICE ADDRESSING

Each ANN-BUS device requires a unique address (ID Num- ber) in order to communicate with the FACP. A maximum of eight devices can be connected to the FACP ANN-BUS com- munication circuit. See the FACP manual for more information.

WIRE REQUIREMENTS

The N-ANN-RLY connects to the FACP ANN-BUS communica- tions circuit. To determine the type of wire and the maximum wiring distance, calculate the total worst case current draw for all modules on a single 4-conductor bus. Use the table on the following page to determine the maximum distance the mod- ules can be located from the FACP. In general, the wire length is limited by resistance, but for heavier wire gauges, capaci- tance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used.

Refer to the appropriate FACP manual for wiring details.
Ordering Information

N-ANN-RLY Relay Module provides 10 programmable Form C relays.

ANN-MBRLY Optional mounting bracket.

DN-7107:A • 1/10/08 — Page 1 of 2