Honeywell PRO-2200 installation manual Cable Specifications

Models: PRO-2200

1 16
Download 16 pages 41.44 Kb
Page 14
Image 14
Cable Specifications

14

Installation Guide

PRO-2200 Power Supply With Battery Backup PRO22E1PS

Cable Specifications

Application

NCI Part No.

AWG

Description

Max. Dist.

Imp.

Cap.

 

N-485 connections

 

NC2442-TN

N/A

Belden 9842

4000' (1200 m)

120Ω

12.8pf/ft

 

 

 

N/A

or equivalent

 

 

 

 

 

CR-1, TR-1, CI-1,

KR-1

NC1861-BL

18

6 conductor shielded

500'

(152 m)

 

 

 

Wiegand card readers

 

 

 

 

 

 

 

 

NR-1 magstripe reader

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

PR-1-280 Cotag reader:

 

 

 

 

 

 

 

 

280 read head to SZC

NC1861-BL

18

6 conductor shielded

300'

(91 m)

 

 

 

SZC to N-1000-II

 

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

PR-2 Hughes reader:

 

 

 

 

 

 

 

 

scanner to reader

 

NC1861-BL

18

6 conductor shielded

30' (9 m)

 

 

 

reader to N-1000-II

 

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

PR-3, PR-5 Indala readers:

 

 

 

 

 

 

 

 

A-3/A-5 read head to RE-2

NC18121-YL

18

12 conductor shielded

75' (23 m)

 

 

 

RE-2 to N-1000-II

 

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

PR-20 , PR-22 Indala readers:

 

 

 

 

 

 

 

 

A-20/A-22 read head

 

 

 

 

 

 

 

 

to RE-2

 

NC18121-YL

18

12 conductor shielded

75' (23 m)

 

 

 

RE-2 to N-1000-II

 

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

PR-10, PR-12 Indala readers:

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

HG-3 hand geometry reader:

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

5 conductor keypad

NC1861-BL

18

6 conductor shielded

500' (152 m)

 

 

 

Alarm input points

 

NC 2221-BR

22

2000' (610 m)

 

 

 

 

 

Relay outputs

 

NC 1821-OR

18

twisted pair, shielded

2000' (610 m)

 

 

 

NOTE: For Plenum rated cable just add a “P” to Northern’s part number prefix; for example NC1861-BL becomes PNC1861-BL

Page 14
Image 14