3 69-0580—2letter code is located near each subbase terminal for identi-fication. The terminal barrier permits straight or conven-tional wraparound wiring connection (Fig. 4).2. Some Q674 Subbases have RC and RH terminalsfor isolated heating and cooling transformers. For zoningsystems, jumper RC and RH terminals as shown in Fig. 5and wire as single R terminal.3. Firmly tighten each terminal screw.4. Fit wires as close as possible to the subbase. Pushexcess wire back into hole.5. Plug the hole with nonflammable insulation to pre-vent drafts from affecting the thermostat.

Fig. 5—Jumper RC and RH terminals for single

transformer system. Strip wire 3/4 in. [19 mm].

RCRH

RCRH

M929

Fig. 6—Typical hookup for MM-2 Mini-zone Control Panel with T874A Thermostat/Q674B,D Subbase in

single-stage heating-cooling two-zone system.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION.
JUMPER RC AND RH TERMINALS TOGETHER AND WIRE AS SINGLE R TERMINAL.
DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL.
1
1
M1633
HEAT
RELAY COOL
RELAY ZONE 1
RELAY ZONE 2
RELAY
Y2
Y1
O
G2
G1
RC
RH
B
W2
W1
E
T6
T5
T4
M6
M4
M1
T6
T5
T4
M6
M4
M1
O1
G1
B1
B
2
1
CHANGEOVER
CONTROL
COOL
FAN
HEAT
24 V, 40 VA
TRANSFORMER
MINIZONE
(MM-2)
CONTROL
PANEL
456Z
DAMPER
ACTUATOR
123X
456Z
DAMPER
ACTUATOR
123X
L2
L1
(HOT)
2
ZONE 2ZONE 1
3
4
OGBY1 RC RH W1
4
T874A THERMOSTAT/Q674B SUBBASE
2
Y1 Y2 RC RH W2
4
T874A THERMOSTAT/
Q674D SUBBASE
3
TO SINGLE-
STAGE
HEATING/
COOLING
EQUIPMENT
W2 Y2 W1
3

Fig. 4—Wiring connections.

FOR STRAIGHT
INSERTION–
STRIP 5/16 in. [8 mm] FOR WRAPAROUND–
STRIP 7/16 in. [11 mm]
SUBBASE TERMINAL SCREW
M928
BARRIER