3 60-2481—2
R182J, R482J, R845A, R847A, R882J, RA89A, RA832A
SPECIFICATIONS • INSTALLATION
a IMPORTANT: The transformer on the R182 can over-
heat when used with a series 20 thermostat if the
total resistance of the thermostat (including thermo-
stat wire and thermostat contact resistance) exceeds
2.5 ohms, add a 100 ohm, 10 watt resistor between
the W and R terminals. Table 2 gives maximum
thermostat wire runs; if longer runs are necessary,
measure the resistance or add a 100 ohm, 10 watt
resistor across terminals W and R.
See Table 2 for the ratings of built-in transformer (all
transformers are rated at 120/240V, 50/60 Hz).
TABLE 2—TRANSFORMER RATINGS.
Fig. 1—Approximate mounting dimensions in
in. [mm].
4
[114]
1
2
1
[48]
7
8
3
8[10]
3
8[10]
5
32
1 [29]
1
4
4 [108]
1
2
3 [89]
5
[133]
1
4
3
32[2] DIAMETER
1
2[13] DIAMETER KEYHOLE TYPE
MOUNTING HOLE
7
8[22] DIAMETER
7
32[6] DIAMETER MOUNTING HOLE
1
[48]
7
8
25
32[20] KNOCKOUT FOR
1/2 (13) CONDUIT (3)
3
8
1 [35] M3823
2
[75]
15
16
WHEN INSTALLING THIS PRODUCT …
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out product operation.
Transformer Rating (watts)
R847A 7.0
RA89A 5.0
RA832A —
R845A —
R182J 6.5
FINISH: Gray enamel.
KNOCKOUTS:
Case bottom: (2) RA89A, RA832A, R845A; (3) Rl82J,
R482J, R882J.
All models have 1 wiring hole in case top.
All knockouts are for 1/2 in. [12.7 mm] conduit.
APPROVALS:
Underwriters Laboratories Inc. Listed: RA89A; RA832A,
R882J; R845A: File no. E4436, Guide no. XAPX.
R482J: File no. E14480, Guide no. NLDS.
R847A: File no. SA481, Guide no. SDFY.
Canadian Standards Association Certified: R482J; R882J;
R847A: File no. LR1620.
InstallationWARNING
ELECTROCUTION HAZARD.
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Transformer core not bonded.
Disconnect power supply before wring to prevent
electrical shock or equipment damage.