S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05 26
Pump Configuration Parameters
Table 17 displays Pump configuration parameters. Use the left
and right arrows to switch between Central Heat, Boiler, DHW,
System, Auxiliary 1, and Auxiliary 2 pumps. The parameters
are the same for all pumps.
Pressing the Advanced Settings button brings up a number of
other advanced configuration options for each pump. Press the
Control Settings button to return to the screen shown in Fig.
45.
Fig. 45. Pump configuration.
*Table 61 on page 53 has more parameters listed.
NOTE: The R7911 Steam Control does not have pumps, but
the outputs are available to operate air dampers or
accessories. CH Pump, Boiler Pump and System
Pump are used for these output options.
Table 17. Pump Configuration Parameters for
R7910A Hydronic System.
Parameter Comment
Pump control Auto
On
Pump output Pump A
Pump B
Pump C
None
Pump start delay ___hour ___min ___sec
Overrun time ___hour ___min ___sec
Table 17a. Pump Configuration Parameters for R7911
Steam Modulation Configuration Parameters.
Parameter Comment
Auxiliary pump control Auto
On
Auxiliary pump is on when CH pump is ON
Slave command
Auxiliary pump output Pump A
Pump B
Pump C
None
Boiler pump control Auto
On
Boiler pump output Pump A
Pump B
Pump C
None
Boiler pump overrun time 0-600 seconds
0 = Not configured
CH pump control Auto
On
CH pump output Pump A
Pump B
Pump C
None
CH pump overrun time 0-600 seconds
0 = Not configured
System pump control Auto
On
System pump output Pump A
Pump B
Pump C
None
System pump ourrun time 0-600 seconds
0 = Not configured
Pump exercise time 0-600 seconds
0= Not configured