B.2 International Electrotechnical Commission (IEC) Classification of Hazardous Locations, Continued

IEC Temperature Classification

Certification and Conformity Details

Equipment intended for installation directly within the hazardous location must also be classified for the maximum surface temperature that can be generated under normal or fault conditions as referenced to the maximum operating ambient of the equipment. The maximum surface temperature must be less than the minimum autoignition temperature of the hazardous atmosphere present. The temperature shall be indicated in identification numbers as listed in the following table.

 

Maximum Temperature

Identification Number

 

 

Degrees C

Degrees F

 

 

 

 

 

 

 

 

 

 

450

842

T1

 

 

 

 

 

 

 

300

572

T2

 

 

 

 

 

 

 

200

392

T3

 

 

 

 

 

 

 

135

275

T4

 

 

 

 

 

 

 

100

212

T5

 

 

 

 

 

 

 

85

185

T6

 

 

 

 

 

 

 

 

 

 

 

Table B-3

CENELEC / LCIE Certification

 

 

 

 

 

 

Code

 

Description

 

3D

Flameproof, Supply 45 Vdc, IP 66/67EEx d IIC T6.

 

 

 

 

 

3A

Intrinsically Safe EEx ia IIC T5, 40 Ta 93°C.

 

 

Flameproof, Supply 45 Vdc, IP 66/67 EEx d IIC T6.

 

 

 

 

 

 

 

 

 

 

LCIE Intrinsic Safety Parameters (1)

 

 

Ui = 30 V

 

 

 

 

Ii = 100 mA

 

 

 

 

Pi = 1.2 W

 

 

 

 

Ci = 4.2 nF

 

 

 

 

Ri = 0

 

 

 

 

Li = 0

 

With no integral indicator, or with

 

 

 

 

integral Smart Meter, option SM.

 

 

Li = 150 H

 

With Analog Meter, option ME.

 

 

 

 

 

(1)Install in accordance with Honeywell drawing 51204243.