4.1 Mounting ST 3000 Transmitter, Continued
Precautions for Mounting Transmitters with Small Absolute or Differential Pressure Spans, continued
For a transmitter with a small differential pressure span, you must ensure that the transmitter is vertical when mounting it. You do this by leveling the transmitter
Table 9 | Zero Corrects Procedure for STD110 | ||||||
|
|
|
|
|
|
|
|
| Step |
|
|
| Action |
| |
|
|
|
|
|
|
| |
| 1 | Attach the transmitter to the mounting bracket but do not completely | |||||
|
| tighten the mounting bolts |
| ||||
| 2 | Connect a tube between the input connections in the high pressure | |||||
|
| (HP) and low pressure (LP) heads to eliminate the affects of any | |||||
|
| surrounding air currents. |
| ||||
| 3 | Connect 24 Vdc power to the transmitter and connect a digital | |||||
|
| voltmeter or SFC to read the transmitter’s output. See Figure 1 for | |||||
|
| typical SFC connection or connect a voltmeter across the 250 ohm | |||||
|
| resistor, if desired. |
| ||||
| 4 | Use the SFC (or SCT) and establish communications with the | |||||
|
| transmitter. Follow the steps in Table 2, if needed. | |||||
| 5 | While reading the transmitter’s output on an SFC or a voltmeter, | |||||
|
| position the transmitter so the output reading is at or near zero and | |||||
|
| then completely tighten the mounting bolts. | |||||
| 6 | Do an input zero correct function using the SFC and following the | |||||
|
| steps below. This corrects the transmitter for any minor error that | |||||
|
| may occur after the mounting bolts are tightened. | |||||
| 7 |
|
|
|
|
|
|
|
|
|
| ^ |
| ||
|
| Initiate shift key selection. Press | SHIFT | key | |||
|
|
| |||||
|
|
| |||||
|
|
| INPUT |
|
|
| |
|
|
| J |
|
|
|
|
|
|
| OUT- |
|
|
|
|
|
| Press | PUT |
| key. Read applied input pressure. | ||
|
| RESET | |||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
| Press | RECT | key. Prompt asks if the applied input pressure equals | |||
|
|
| |||||
|
| zero input. If it is zero input, go to next keystroke. If it is not, press | |||||
|
| [CLR] key to exit function and repeat keystrokes. | |||||
|
|
|
|
|
| ||
|
|
| ENTER |
|
|
|
|
|
| Press | (Yes) |
| key. Zero input is set equal to applied input pressure. | ||
|
|
|
| ||||
|
|
|
| ||||
|
|
| |||||
| 8 | Remove the tube from between the input connections, the power, | |||||
|
| and the digital voltmeter or SFC. |
| ||||
| 9 | Continue with the remaining installation tasks. | |||||
|
|
|
|
|
|
|
|
Continued on next page