T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3
11
5. Press the increase ▲ key again to display the
EEPROM identification code.
(Example: 222 = EEPROM ID 222).
Table 8. Installer Self-Test Options.
M4867
6. Press and hold the increase ▲ and decrease ▼ keys
together, until the room temperature is displayed, to exit
the Self-Test. The Self-Test times out after five minutes
without any key presses.
aAvailable on select models.
Key to
Press Test
Number Description
Heating Equipment Self-Test
i 10 Enter heating equipment Self-Test.
▲ 11 Stage-one heat turns on. When Installer Setup number 01 is 01 or 02 is 01, the system fan is
also energized.
▲ 12 Stage-two heat turns on. Stage-one heat and system fan remain on.
▲ 13 Stage-three heat turns on. Stage-one and stage-two heat remain on.
▼ 12 Stage-three heat turns off.
▼ 11 Stage-two heat turns off.
▼ 10 Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test (with select models of Q7100C subbase)
i 20 Change from heating to emergency heating equipment Self-Test.
▲21 Emergency heat turns on. System fan also turns on.
▼20 Emergency heat turns off.
Cooling Equipment Self-Test
i 30 Change from heating or emergency heating to cooling equipment Self-Test.
▲ 31 Stage-one cool and system fan turn on.
▲ 32 Stage-two cool and system fan turn on.
▼ 31 Stage-two cool and system fan turn off.
▼ 30 Stage-one cool and system fan turn off.
Fan Equipment Self-Test
i 40 Change from cooling to fan equipment Self-Test.
▲ 41 Fan turns on.
▼ 40 Fan turns off.
Key Test
a
i 60 Displays 2.
▲60 Displays 4.
▼60 Displays 3.
Override 60 Displays 5.
System
a
60 Displays 0.
Fan
a
60 Displays 1.