T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3
11
5. Press the increase key again to display the
EEPROM identification code.
(Example: 222 = EEPROM ID 222).
Table 8. Installer Self-Test Options.
M4867
6. Press and hold the increase and decrease keys
together, until the room temperature is displayed, to exit
the Self-Test. The Self-Test times out after five minutes
without any key presses.
aAvailable on select models.
Key to
Press Test
Number Description
Heating Equipment Self-Test
i 10 Enter heating equipment Self-Test.
11 Stage-one heat turns on. When Installer Setup number 01 is 01 or 02 is 01, the system fan is
also energized.
12 Stage-two heat turns on. Stage-one heat and system fan remain on.
13 Stage-three heat turns on. Stage-one and stage-two heat remain on.
12 Stage-three heat turns off.
11 Stage-two heat turns off.
10 Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test (with select models of Q7100C subbase)
i 20 Change from heating to emergency heating equipment Self-Test.
21 Emergency heat turns on. System fan also turns on.
20 Emergency heat turns off.
Cooling Equipment Self-Test
i 30 Change from heating or emergency heating to cooling equipment Self-Test.
31 Stage-one cool and system fan turn on.
32 Stage-two cool and system fan turn on.
31 Stage-two cool and system fan turn off.
30 Stage-one cool and system fan turn off.
Fan Equipment Self-Test
i 40 Change from cooling to fan equipment Self-Test.
41 Fan turns on.
40 Fan turns off.
Key Test
a
i 60 Displays 2.
60 Displays 4.
60 Displays 3.
Override 60 Displays 5.
System
a
60 Displays 0.
Fan
a
60 Displays 1.