Crop-trol Controllers
T675F
Used to control an
•Suitable for
•Mounts directly on dryer with sensing bulb in discharge air duct.
•Knob extends through case for manual control
point adjustment.
•Differential setting wheel, located under cover, adjusts difference between
Generic remote bulb controllers
T675, T678
Regulate temperature of air or liquids in ducts, pipes, tanks and boilers.
•Suitable for applications requiring temperature control of air or liquids where controller must be placed outside the sensing area.
•Typical uses include control of dampers and valves in heating, cooling and
•Fast response models (available for use in return air duct) operate approximately four times faster than standard models.
•Controller can be mounted in any position.
•Ambient temperature compensation provides good temperature control.
Remote Temperature Controllers
|
|
|
| Capillary |
|
| |
| Setpoint | Relay |
| Length |
|
| |
Part Number | Temperature | Outputs | Element Type | (Feet) | Differential (˚F) | Comments | |
|
|
|
|
|
|
| |
T675A1045 | 0˚ F to 100˚ F | 1 SPDT | Stainless steel bulb | 20 ft | 3˚ F to 10˚ F | Stainless Steel Bulb | |
|
|
|
|
|
|
| |
T675A1102 | 160˚ F to 260˚ F | 1 SPDT | Copper bulb | 20 ft | 3˚ F to 10˚ F |
| |
|
|
|
|
|
|
| |
T675A1136 | 0˚ F to 100˚ F | 1 SPDT | Copper bulb | 20 ft | 1˚ F fixed |
| |
|
|
|
|
|
|
| |
T675A1425 | 55˚ F to 175˚ F | 1 SPDT | Copper bulb | 20 ft | 3.6˚ F to 12˚ F |
| |
|
|
|
|
|
|
| |
T675A1458 | 55˚ F to 175˚ F | 1 SPDT | Copper bulb | 5 ft | 1˚ F fixed |
| |
|
|
|
|
|
|
| |
T675A1508 | 0˚ F to 100˚ F | 1 SPDT | Copper bulb | 5 ft | 3˚ F to 10˚ F | Includes 107324A Duct Bulb Holder | |
|
|
|
|
|
|
| |
T675A1516 | 0˚ F to 100˚ F | 1 SPDT | Copper bulb | 5 ft | 1˚ F fixed | Includes 107324A Duct Bulb Holder | |
|
|
|
|
|
|
| |
T675A1524 | 55˚ F to 175˚ F | 1 SPDT | Copper bulb | 20 ft | 1˚ F fixed |
| |
|
|
|
|
|
|
| |
T675A1532 | 160˚ F to 260˚ F | 1 SPDT | Copper bulb | 5 ft | 3˚ F to 10˚ F | Includes 107324A Duct Bulb Holder | |
|
|
|
|
|
|
| |
T675A1540 | 55˚ F to 175˚ F | 1 SPDT | Copper bulb | 5 ft | 3.6˚ F to 12˚ F | Includes 107324A Duct Bulb Holder | |
|
|
|
|
|
|
| |
T675A1565 | 0˚ F to 100˚ F | 1 SPDT | Copper bulb | 20 ft | 3˚ F to 10˚ F | Includes 107324A Duct Bulb Holder | |
|
|
|
|
|
|
| |
T675A1706 | 0˚ F to 100˚ F | 1 SPDT | Fast response capillary | 5 ft | 3˚ F to 10˚ F | Fast response model, includes | |
107324A Duct Bulb Holder | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
T675A1722 | 55˚ F to 175˚ F | 1 SPDT | Fast response capillary | 5 ft | 3.6˚ F to 12˚ F | Fast response model, includes | |
107324A Duct Bulb Holder | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
T675A1771 | 55˚ F to 175˚ F | 1 SPDT | Fast response capillary | 5 ft | 1˚ F fixed | Fast response model, includes | |
107324A Duct Bulb Holder | |||||||
|
|
|
|
|
| ||
T675A1920 | 1 SPDT | Copper bulb | 20 ft | 1.7˚ C to 5.6˚ C | |||
|
|
|
|
|
|
| |
T675A2068 | 1 SPDT | Copper bulb | 1.5 m | 1.7˚ C to 5.6˚ C | Celsius model | ||
|
|
|
|
|
|
| |
T675A2076 | 1 SPDT | Copper bulb | 1.5 m | 0.6˚ C fixed | Celsius model | ||
|
|
|
|
|
|
| |
T675A2084 | 1 SPDT | Copper bulb | 6.1 m | 1.7˚ C to 5.6˚ C | Celsius model | ||
|
|
|
|
|
|
| |
T675A2100 | 15˚ C to 75˚ C | 1 SPDT | Copper bulb | 1.5 m | 2˚ C to 6.6˚ C | Celsius model | |
|
|
|
|
|
|
| |
T675A2118 | 75˚ C to 125˚ C | 1 SPDT | Copper bulb | 1.5 m | 1.7˚ C to 5.6˚ C | Celsius model | |
|
|
|
|
|
|
| |
T675B1002 | 30˚ F to 50˚ F | 1 SPDT | Copper bulb | 10 ft | Manual Reset |
| |
|
|
|
|
|
|
| |
T675B1010 | 30˚ F to 50˚ F | 1 SPDT | Copper bulb | 20 ft | Manual Reset |
| |
|
|
|
|
|
|
| |
T675B1028 | 1 SPDT | Copper bulb | 10 ft | Manual Reset |
| ||
|
|
|
|
|
|
| |
T675F1032 | 80˚ F to 220˚ F | 1 SPDT | Copper bulb | 10 ft | 5˚ F to 30˚ F |
| |
|
|
|
|
|
|
| |
T678A1015 | 0˚ F to 100˚ F | 2 SPDT | Copper bulb | 20 ft | Switch: 3˚ F fixed/Interstage: 3˚ F to 10˚ F adjustable |
| |
|
|
|
|
|
|
| |
T678A1155 | 2 SPDT | Copper bulb | 5 ft | 3˚ F | |||
|
|
|
|
|
|
| |
T678A1163 | 5˚ F to 95˚ F | 2 SPDT | Copper bulb | 6.1 m | Switch: 1.7˚ C fixed/Interstage: 1.7˚ C to 5.6˚ C adjustable | Celsius model | |
|
|
|
|
|
|
| |
T678A1353 | 55˚ F to 175˚ F | 2 SPDT | Copper bulb | 5 ft | 3.6˚ F |
| |
|
|
|
|
|
|
| |
T678A1361 | 55˚ F to 175˚ F | 2 SPDT | Copper bulb | 20 ft | Switch: 3.6˚ F fixed/Interstage: 3.6˚ F to 12˚ F adjustable |
| |
|
|
|
|
|
|
| |
T678A1395 | 15˚ C to 75˚ C | 2 SPDT | Copper bulb | 1.5 m | 2˚ C | Celsius model | |
|
|
|
|
|
|
| |
T678A1437 | 0˚ F to 100˚ F | 2 SPDT | Copper bulb | 5 ft | Switch: 3˚ F fixed/Interstage: 3˚ F to 10˚ F adjustable |
| |
|
|
|
|
|
|
| |
T678A1445 | 55˚ F to 175˚ F | 2 SPDT | Copper bulb | 5 ft | Switch: 3.6˚ F fixed/Interstage: 3.6˚ F to 12˚ F adjustable |
| |
|
|
|
|
|
|
| |
T678A1478 | 0˚ F to 100˚ F | 2 SPDT | Fast response capillary | 5 ft | Switch: 3˚ F fixed/Interstage: 3˚ F to 10˚ F adjustable | Fast response model | |
|
|
|
|
|
|
| |
T678A1494 | 55˚ F to 175˚ F | 2 SPDT | Fast response capillary | 5 ft | Switch: 3.6˚ F fixed/Interstage: 3.6˚ F to 12˚ F adjustable | Fast response model | |
|
|
|
|
|
|
| |
T678A1627 | 0˚ F to 100˚ F | 2 SPDT | Averaging capillary | 10 ft | Switch: 3.6˚ F fixed/Interstage: 3.6˚ F to 12˚ F adjustable |
| |
|
|
|
|
|
|
| |
T678A1692 | 15˚ C to 7˚5 C | 2 SPDT | Copper bulb | 1.5 m | 2˚ C | Celsius model | |
|
|
|
|
|
|
| |
T678C1005 | 55˚ F to 85˚ F | 2 SPDT | Copper bulb | 5.5 ft | 5˚ F | Changeover Stat | |
|
|
|
|
|
|
| |
T678F1002 | 55˚ F to 85˚ F | 2 SPDT | Copper bulb | 5.5 ft | 2.0˚ F |
| |
|
|
|
|
|
|
|