T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
5 69-1465—3
3. Setting Number of Cool/Heat Stages (T8024F
Only).
a. Press to display number of cool stages.
b. Press to change number of cool stages.
c. Press to display number of heat stages.
d. Press to change number of heat stages.
4. Setting Heat Cycle Rate (see Table 2) for the cycle
rate options and equipment.
a. Press the key to display the current heat
cycle rate setting of 1,3, 4, 5, 6, 9, or 12 cph.
NOTE: If thermostat is set to operate two stages of heat
(T8024 only), both stages operate at the
selected cycle rate.
b. To change the heat cycle rate, press the key
until your choice of 1, 3, 4, 5, 6, 9, or 12 is dis-
played. See Table 2.
c. Press the key to display control algorithm
configuration default.
d. Press the key again to change control algo-
rithm to C1 or C3.
C1 = Standard control algorithm.
C3 = Aggressive control algorithm (can
cause overshooting).
e. Press the key again. Current configuration
(CC) is displayed. A typical example is shown,
but CC varies by model. (This information is for
factory use only.)
5. Exit Installer Setup.
a. Press the key to save all changes and return
to normal operation.
Table 2. Heating Cycle Rate
aHigh efficiency furnace (90+).
bRefer to the equipment manufacturer’s instructions.
M2021
6
M2021
5
M2021
7
M2021
8
M12589
A
System Cycles Per Hour
Steam, gravity 1
Hydronic heat, condensing gas
furnacesa
3
Gas or oil forced air 6
Electric heat 9
Special applicationsb4, 5, 12
M12588
A
M1469
1
M1469
2
M12590A
PM