69-1055—1 6
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Installer Setup
Number
(Press i key Factory-Setting Other Choices
(Press or key to change) Actual
Select to change) Display Description Display Description Setting
Heating
setpoint range
stopa
34 90 Heating setpoint can be
set no higher than 90°F 40 thru
90 Number can be set
anywhere between 40 and
90 in 1°F increments
Cooling
setpoint range
stopa
35 45bCooling setpoint can be
set no lower than 45°Fb45b thru
99 Number can be set
anywhere between 45b and
99 in 1°F increments
Not used 36
Temperature
display
adjustment
37 00 No difference in
displayed temperature
and actual room
temperature
-3 thru
3
1—Display adjusts to 1°F
higher than actual room
temperature
2—Display adjusts to 2°F
higher than actual room
temperature
3—Display adjusts to 3°F
higher than actual room
temperature
-1—Display adjusts to 1°F
lower than actual room
temperature
-2—Display adjusts to 2°F
lower than actual room
temperature
-3—Display adjusts to 3°F
lower than actual room
temperature
Table 2. Thermostat Installer Setup Options (continued).

Em HeatOffCool Auto Only

Heat Cool

OnAuto

System Fan

Room

Outdoor

Em Ht Temporary Setting

Wait

%Humid

Aux Ht Remote

Repl

Batt

M4844
M6792
TEST MODE
NUMBER
a Available on select models.
b T8524D is 48°F (9°C).
IMPORTANT

Review the settings to confirm that they match

the system.

INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
To start the system test::
NOTE: The minimum off time for compressors is
bypassed during the Installer System Test.
Press and hold the increase and decrease keys, at
the same time, until two zeros appear. All segments of the
LCD are displayed before the two zeros appear.
Test
Number System Test Description
10-19 Heating equipment can be turned on and off
30-39 Cooling equipment can be turned on and off
40-49 Fan equipment (T8524D only) can be turned
on and off.
60-69 System key or system switch position test
70-79 Thermostat information including date code
and software versions are displayed
IMPORTANT

T8524C models must set the switches to the

equipment that is being checked for the equip-

ment to operate.

NOTE: Press and hold the increase and decrease
keys for three seconds to exit the System Test.
The System Test times out after five minutes
without any key presses.
Table 3. Tests Available In The Installer System Test.