T8624D CHRONOTHERM
®
IV DELUXE PROGRAMMABLE THERMOSTAT
68-0166—1
11
Table 8. Installer System Test Options.
3. Press the increase key again to display the software
identification code. (Example: 02 = software ID code 2)
NOTE: Press any key and the displayed numbers will
change. Press Time to go to the previous test
and Time to go to the next test. The Run
Program key will not exit from this test. To exit, go
to a different test and press Run Program.
Thermostat Information
1. Press the Time key to access the thermostat
information.
Key to
Press Test
Number Description
Heating Equipment System Test
Time 10 Enter heating equipment system test.
11 Stage-one heat comes on. The system fan is also energized.
12 Stage-two heat comes on. Stage-one heat and system fan remain on.
11 Stage-two heat turns off.
10 Stage-one heat and system fan turn off.
Cooling Equipment System Test
Time 30 Change from heating to cooling equipment system test.
31 Stage-one cool and system fan come on.
32 Stage-two cool comes on. Stage-one cool and system fan remain on.
31 Stage-two cool turns off.
30 Stage-one cool and system fan turn off.
Fan Equipment SystemTest
Time 40 Change from cooling to fan equipment system test.
41 Fan comes on.
40 Fan turns off.
Key Operation System Test
Time 60 2 Change from fan to key operation system test.
M4934
2. Press the increase key to display the production
date code. The first two large digits are the month and
the third digit is the last digit of the year (Example:
027=February 1997).
M10351
M4932A
4. Press the increase key again to display the software
revision number (Example: 001=Revision number 1).
M10229
5. Press the increase key again to display the
EEPROM identification code. (Example: 314 =
EEPROM ID 314)
M4933A
6. Press the Run Program key to exit the system test.
The system test times out after four minutes without
any key presses.