T8624D CHRONOTHERM
®
IV DELUXE PROGRAMMABLE THERMOSTAT
68-0166—1
9
Table 6. Thermostat Installer Setup Options (continued).
IMPORTANT
Review the settings to confirm that they match the
system. Press Run Program to exit the Installer
Setup. The thermostat has saved the Installer Setup
changes and initiated a reset in order to operate with
these new settings. Be sure to set the current day
and time immediately.
Setting Current Day and Time
1. Press Set Current Day/Time.
NOTE: On initial power up or after an extended power
loss, 1:00 pm flashes on the display until a key
is pressed.
M10312
Time Set Program
System Fan
Run
Program
Hold Temp
Set Current
Day/Time
Set Current
Day/Time
Wake Leave Return Sleep
Day Heat/Cool
Settings
Daylight
Time Copy
Mon
PM
Set Day/Time
Installer Setup
Number (Press
Time key to Factory-Setting Other Choices
(Press or key to change) Actual
Select change) Display Description Display Description Setting
Not used 31 and 32
Minimum off time
for the compressor 33 5 5 minute minimum off
time for the
compressor
0 thru 4 Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor
Temperature range
stops in heating 34 90 Highest setpoint
heating can be set to 40 to 89 Temperature range (1°F
increments) heating setpoint
can be set to
Temperature range
stops in cooling 35 45 Lowest setpoint
cooling can be set to 46 to 99 Temperature range (1°F
increments) cooling setpoint
can be set to
Not used 36
Temperature
display adjustment 37 0 No difference in
displayed temperature
and actual room
temperature
-3 thru 3 1—Display adjusts to 1°F
higher than actual room
temperature
2—Display adjusts to 2°F
higher than actual room
temperature
3—Display adjusts to 3°F
higher than actual room
temperature
-1—Display adjusts to 1°F
lower than actual room
temperature
-2—Display adjusts to 2°F
lower than actual room
temperature
-3—Display adjusts to 3°F
lower than actual room
temperature