Move the system switch to COOL and the fan switch to
AUTO. Press COOLER key until the setting is about
10° F [6° C] below room temperature. The cooling equip-
ment and fan should start. Press WARMER key until the
setting is about 10° F [6° C] above room temperature. The
cooling equipment and fan should stop.
FAN
Move the system switch to OFF, and the fan switch to
ON. The fan should run continuously. When the fan switch
is in the AUTO position, fan cycles with the heating or
cooling system.
EXTERNAL ACCESS AND CONTROL
A triangle symbol is displayed on the lower right
corner of the LCD when the T8631 setting has been
adjusted through the TotalHome system. See Fig. 11.
INSTALLER SELF-TEST (OPTIONAL)
NOTE: Thermostat must have AC power to perform
self-test.
Perform the following test as a check of all thermostat
functions. If thermostat does not respond as indicated,
thermostat must be replaced.
1. Press AHEAD and BACK keys at the same time.
While holding keys down, all segments of the display
should be on. See Fig. 11.
2. Set system switch to OFF. Press AHEAD and BACK
and PRESENT SETTING keys at the same time to enter
self-test.
3. Press each key as listed below, and look for re-
sponses listed as key is held down and released.
Look For This Response
Press This Key Key Down Key Released
PRESENT SETTING 15 see notea
following
SKIP NEXT PERIOD 07 blank
CHANGE TO LAST 03 blank
PERIOD
COOLER 02 blank
WARMER 06 serial number
transmitted
on HBus
BACK 04 blank
AHEAD 05 blank
RETURN 00 blank
LEAVE 01 control micro-
processor mask
number and
revision number
SLEEP 08 blank
WAKE 12 see noteb
following
SET HEAT/COOL 09 blank
DAY 13 interface
micro-
processor
mask number
and revision
number
HOLD TEMP 10 blank
SET PRESENT 14 see notec
DAY/TIME following
RUN PROGRAM 11 normal operat-
ing display
NOTES:
aIf the system switch is in COOL, the following se-
quence will occur:
6
Fig. 11All segments on display.
SUN MON TUE WED THU FRI SAT COOL ON HEAT ON
WAKE LEAVE RETURN SLEEP TEMPORARY
REPL
BAT
AM
PM
SET
PT
M410C