BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
63-4524—01 20
Standard Object Types Supported Table 6. Standard object types supported.
a Present_Value and Out_of_Service properties are writable for every AV objects except :
• PI Heating Demand (AV21)
• PI Cooling Demand (AV22)
bPresent_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if Room Temp
Override (BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
cObject_Name property is writable for the following object only :
• Room Temperature (AV7)
dPresent_Value and Out_of_Service properties are writable for every MV objects except :
• Heating Valve Status (MV26)
• Cooling Valve Status (MV27)
• Fan Status (MV28)
• Effective Occupancy (MV33)
List of Proprietary PropertiesTable 7. Proprietary Properties.
Object Type Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported
Writable Properties
Analog Input
Reliability Out_of_Service
Analog Value
Reliability
Present_Valuea,b
Out_of_Servicea
Object_Namec
Binary Input
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group N/A N/A
Multi-state Value
Reliability
States_Text
Present_Valued
Out_of_Serviced
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString The version number of the BACnet communications
module. This is the hardware version number
MS/TP_Address 1001 Unsigned Display the MAC layer add ress of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration value.
The range is –5.0 deg F to 5.0 deg F for a temperature
and –15% to 15% for humidity.