BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
963-4524—01
INTEGRATIONGlobal Commands
The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front-end.
Fig. 6. Global commands from a BAS front-end to a typical TB7300 Series thermostat.
GLOBAL COMMAND CONTROL LEVEL DEVICE LEVEL
BAS FRONT-END
MSTP NETWORK
GLOBAL COMMANDS ALL DEVICES
(ALL THERMOSTATS)
OUTDOOR TEMPERATURE
OUTDOOR TEMPERATURE AND OUTDOOR HUMIDITY (ENTHALPY)
OUTDOOR TEMPERATURE AND HVAC PLANT CURRENT MODE
GLOBAL COMMANDS SPECIFIC DEVICES
(SPECIFIC AREA THERMOSTATS)
SCHEDULE
SCHEDULE AND OUTDOOR TEMPERATURE
OCCUPANCY (MV18)
FAN MODE (MV17)
OCCUPIED HEATING SETPOINT (AV39)
UNOCCUPIED HEATING SETPOINT (AV43)
OCCUPIED COOLING SETPOINT (AV40)
UNOCCUPIED COOLING SETPOINT (AV44)
KEYPAD LOCKOUT (MV19)
ROOM TEMPERATURE (AV7)
AUX OUTPUT (BV14)
MCR32655
TB7300 SERIES TSTAT
OUTDOOR TEMPERATURE (AV9)
DEHUMIDIFICATION LOCKOUT (BV13)
SEQUENCE OF OPERATION (MV15)
SYSTEM MODE (AV16)
RESTRICT USER ACCESS TO THERMOSTAT
ROOM TEMPERATURE FOR TESTING AND OVERRIDE
REMOTE CONTROL OF THE AUXILIARY OUTPUT