TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
11 62-3070—03
0340 Remote
Temperature
Sensor
0 0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
Averaging would not include on-board sensor. It is
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing
compressor lockout while displaying temperature).
0350 Heat Pump
Compressor
Lockout
0 0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35(1.5)—35°F (1.5°C)
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
Only shown for heat pump systems with more heat
stages than cool selected and remote sensor
selection is outdoor for control.
Must enforce a dead band between this and
Auxiliary Lockout
0360 Heat Pump
Auxiliary Lockout
0 0—None
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)
Only shown for heat pump systems with more heat
stages than cool selected and remote sensor
selection is outdoor for control.
Must enforce a dead band between this and Heat
Pump Compressor Lockout.
0535 Temporary
Occupied Duration
Limit
3 0—no duration
1—one hour
2—two hours
3—three hours
4��four hours
0 means no limit
0540 Number of Periods 4 2—2 Periods
4—4 Periods
Does not appear if Non-programmable is chosen.
Applies to all days of the week. With 2 selected the
“Cancel Period” option does not appear on the
display.
0580 Minimum
Compressor Off
Time
50Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
Only shown if system has cool stages.
0600 Heat Temperature
Range Stops
90 40 to 90°F (4 to 32°C) Only shown if system has heat stages.
0610 Cool Temperature
Range Stops
50 50 to 99°F (10 to 37°C) Only shown if system has cool stages.
0640 Clock Format 12 12—12 Hour
24—24 Hour
0650 Extended Fan-on
time Heat
00Off
90—90 seconds
Not displayed with fan set to fossil or with cool-only
systems
0660 Extended Fan-on
time Cool
00Off
40—40 seconds
Only shown if system has cool stages.
0670 Keypad Lockout 0 0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.
0680 Temperature
Control Heat
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has heat stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
0685 Recovery Heat
Ramp Rate
5 0-20°F/hour Only shown if system has heat stages.
0 disables ramped recovery (step setpoint change
at period start time).
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes