TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
562-0278—07
Ps: Pipe sensor (optional)
R: 24 Vac power
Rs: Remote sensor (optional)
SB: Remote setback (optional)
Sc: Ground (required if remote sensor, pipe sensor,
and/or remote setback are connected)
W/Y: W = Heating; Y = Cooling (2 pipe only)
Y/A: Y = Cooling; A = Electrical heater output
Table 3. Terminal Wiring.
Model Application
Terminals
1234567891011
TB6575A1000 — 120/240 Vac
TB6575C1000 — 120/240/277 Vac
Terminal Identifier LW/Y Y/AGlGmGhNRs
a
aRs; Remote sensor is optional.
Scb
bRequired when Rs, SB, or Ps is wired.
SBc
cSB; Remote setback is optional.
Psd
dPipe sensor: Discrete, Analog, or Aquastat®.
Fly lead wire color Black Orange Yellow Red Blue Brown White Nonee
eThese terminals (8, 9, 10, and 11) do not have lead wires attached to them.
2 pipes; Heat only f
fA check mark () indicates the terminal is used in that application. Rs and SB terminal connections are optional. If a
terminal is left blank, it is not used in that application.
W  Og
gO = Optional
Rh
hR = Required if Rs, SB, or Ps is wired.
O
2 pipes; Cool only Y ORO
2 pipes; Heat or Cool with Manual Changeover W/Y  ORO
2 pipes; Heat or Cool with Seasonal Changeover W/Y   ORO
4 pipes; Heat and Cool with Manual Changeover WY  ORO
4 pipes; Heat and Cool with Auto Changeover WY  ORO
2 pipes; Heat or Cool with Auxiliary Heat W/Y A  ORO
4 pipes; Heat and Cool with Manual Changeover or
Auto Changeover
WY  ORO
TB6575B1000 — 120/240 Vac
Terminal Identifier L W/Y n/ai
iTerminal 3 is not used on the TB6575B1000 model.
Gl Gm Gh N RsaScbSBcPsd
Fly lead wire color Black Orange Red Blue Brown White Nonee
2 pipes; Heat only W ORO
2 pipes; Cool only Y ORO
2 pipes; Heat or Cool with Manual Changeover W/Y  ORO
2 pipes; Heat or Cool with Seasonal Changeover W/Y   ORO
TB8575A1000 — 24 Vac
Terminal Identifierj
jThe TB8575A1000 model does not have fly lead wires attached to any terminals.
RW/YY/AGlGmGhCRs
aScbSBcPsd
2 pipes; Heat only W ORO
2 pipes; Cool only Y ORO
2 pipes; Heat or Cool with Manual Changeover W/Y  ORO
2 pipes; Heat or Cool with Seasonal Changeover W/Y   ORO
4 pipes; Heat and Cool with Manual Changeover WY  ORO
4 pipes; Heat and Cool with Auto Changeover WY  ORO
2 pipes; Heat or Cool with Auxiliary Heat W/Y A  ORO
4 pipes; Heat and Cool with Manual Changeover or
Auto Changeover
WY  ORO