PRO 1000 Series
9
ENGLISH
In case of difficulty
Screen is blank. Check circuit breaker and reset if necessary.
Ensure the heating/cooling system is powered up.
Ensure the furnace door is properly closed.
Ensure two fresh AAA alkaline batteries are correctly installed.
Temperature settings cannot be
changed.
•The System switch is off.
You are setting the temperatures outside their allowable ranges:
Heat: 40 °F to 90 °F (4.5 °C to 32 °C).
Cool: 50 °F to 99 °F (10 °C to 37 °C).
Cool On or Heat On is flashing. • The compressor protection delay has been activated. Wait for the
delay to end (maximum of 5 minutes).
HI appears on the screen. The ambient (measured) temperature is above 122 °F (50°C).
LO appears on the screen. The ambient (measured) temperature is below 32 °F (0 °C).
E1 appears on the screen. The temperature sensor circuit is opened. Replace the thermostat.
E2 appears on the screen. The temperature sensor circuit is shorted. Replace the thermostat.