Installation Guide
8
10 0
Test
10
20
30
70
Heating system
Emergency heat
Cooling system
Thermostat
information
(for reference only)
0 Compressor and fan turn off.
1 Compressor and fan turn on.
2 Auxiliary heat turns on.
0 Heat and fan turn off.
1 Heat and fan turn on.
2 Auxiliary heat turns on.
0 Compressor and fan turn off.
1 Compressor and fan turn on.
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)

System Test System Status

Installer system test
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
System switch
System test
number
System status

Follow the procedure below to test the heating and cooling system.

1 Set SSYYSSTTEEMMswitch to Heat.
2 Press to turn on and check systems (see table, below).
3 Press until systems turn off.
4 Set SSYYSSTTEEMMswitch to Em Heat and repeat steps 2-3 above.
5 Set SSYYSSTTEEMMswitch to Cool and repeat steps 2-3 above.
5Press and hold to terminate test at any time.