VisionPROTM TH8000 Series
9
Setup functions Settings & Options (factory d efault in bold)
0500 Furnace lter
change reminder
0 Off
1 10-day run time (about 1 month)
2 30-day run time (about 3 months)
3 60-day run time (about 6 months)
4 90-day run time (about 9 months)
5 120-day run time (about 1 year)
6 365-day run time (about 3 years)
0510 Humidier pad
change reminder
0 Off
1 90 calendar days
2 180 calendar days
3 365 calendar days
0520 UV lamp change
reminder
0 Off
1 365 calendar days
0530 Adaptive Intelligent
Recovery™
1 On ** See page 11
0 Off
0540 Program periods 4 4 program periods (Wake, Leave, Return, Sleep)
2 2 program periods (Wake, Sleep)
0580 Compressor
protection
5 5 minute compressor off time ** See page 11
[Other options: 0, 1, 2, 3 or 4-minute off time]
0600 Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4°C to 32°C)]
0610 Cool temperature
range stop
50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (11°C to 37°C)]
0640 Clock format 12 12-hour time (i.e., “3:30 pm”)
24 24-hour time (i.e., “15:30”)
0650 Extended fan
timer (heat)
0 Off
90 Fan runs for 90 seconds after call for heat ends
0660 Extended fan
timer (cool)
0 Off
90 Fan runs for 90 seconds after call for cooling ends
0670 Keypad lock 0 Keypad unlocked (fully functional)
1 Partially locked (access to temperature settings only)
2 Fully locked
0680 Heat temperature
control
2 Standard temperature control (recommended)
1 Choose if room is warmer than set temperature
3 Choose if room does not reach set temperature
0690 Cool temperature
control
2 Standard temperature control (recommended)
1 Choose if room is cooler than set temperature
3 Choose if room does not reach set temperature
0700 Temperature
display offset
0 Thermostat displays actual room temperature
[Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)
0710 RESET 0 No reset
1 Reset installer options & program schedule to factory
default (only date and time settings are retained)
Installer setup