EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
nciSetPnts
nciSetPnts
nciSetPnts
nciSetPnts
nciSetPnts
nciWallMod
nciWallMod
nciWallMod
nciWallMod
field name
standby_cool
unoccupied_cool
occupied_heat
standby_heat
unoccupied_heat
ui_bypass_time
si_low_setpt
si_high_setpt
si_space_temp_zero_ cal
Table C2. Configuration Variables for Excel 10 FCU Controllers
engineering units: | digital |
|
| |
state | default | comments | ||
English (metric) or states | ||||
or | ||||
plus range |
|
| ||
value |
|
| ||
|
|
| ||
SNVT_temp_p |
| 77°F (25°C) | This is the configured setpoint which applies to the standby cooling | |
50 to 95°F (10 to 35°C) |
|
| mode. Where the ZEB for standby is used, it is derived from the | |
|
|
| difference between standby_cool and standby_heat. | |
|
|
|
| |
SNVT_temp_p |
| 82.4°F (28°C) | This is the configured setpoint which applies to the unoccupied cooling | |
50 to 95°F (10 to 35°C) |
|
| mode. | |
|
|
|
| |
SNVT_temp_p |
| 69.8°F (21°C) | This is the default setpoint for the occupied heating setpoint which is | |
50 to 95°F (10 to 35°C) |
|
| used in case there is no locally wired setpoint knob or nviSetpoint has | |
|
|
| not been bound. Where the ZEB for occupied is used, it is derived from | |
|
|
| the difference between occupied_cool and occupied_heat. | |
|
|
|
| |
SNVT_temp_p |
| 66.2°F (19°C) | This is the configured setpoint which applies to the standby heating | |
50 to 95°F (10 to 35°C) |
|
| mode. Where the ZEB for standby is used, it is derived from the | |
|
|
| difference between standby_cool and standby_heat. | |
|
|
|
| |
SNVT_temp_p |
| 60.8°F (16°C) | This is the configured setpoint which applies to the unoccupied heating | |
50 to 95°F (10 to 35°C) |
|
| mode. | |
|
|
|
| |
UWORD |
| 180 min | This configuration variable specifies the time the controller remains in | |
0 to 1080 minutes |
|
| OCCUPIED mode before reverting to the original occupancy mode | |
|
|
| after pressing the override button at the wall module or initiating | |
|
|
| BYPASS via the network. When the bypass mode has been activated, | |
|
|
| the bypass timer is set to ui_bypass_time. When the timer expires, | |
|
|
| nvoFcuStatus.occ_status.hw_override reverts from OC_BYPASS to | |
|
|
| OC_NUL to quit the bypass override function. | |
SNVT_temp_p |
| This configuration variable specifies the low limit for the setpoint knob. | ||
| (53.6°F (12°C) for | It can be relative or absolute depending upon the configuration in | ||
relative |
| absolute setpoint) | nciWallMod.set_pnt_knob. |
53.6to 86°F (12 to 30°C) for absolute
SNVT_temp_p | 9 DDF (5 K) | This configuration variable specifies the high limit for the setpoint knob. |
(86°F (30°C) for | It can be relative or absolute depending upon the configuration in | |
relative | absolute setpoint) | nciWallMod.set_pnt_knob. |
53.6to 86°F (12 to 30°C) for absolute
SNVT_temp_p | 0 DDF (0 K) | The space temperature sensor is corrected by adding this calibration |
| setting (an offset value) to the sensed value. |
45 |