WSK-24 WIRELESS OCCUPANCY SOLUTION INSTALLATION
62-0300ES—01 4
Fig. 3. Receiver and wiring harness.
Using Table3 on page 3 and Fig. 3, wire the harness to
the thermostat and connect the harness to the receiver.
1. Wire the red and white power leads on the wiring
harness into the power terminals on the thermostat.
2. Wire the white/brown and brown dry contact leads
on the wiring harness into the remote setback
terminals on the thermostat.
3. Plug the wiring harness into the receiver. The
harness is keyed and fits only one way.
4. Supply power to the thermostat.
5. The LED on the receiver flashes twice to show it
has power.
6. Continue with “Setting the Delay on the Receiver”.
Setting the Delay on the ReceiverRefer to Fig. 4 and position the jumper to the desired
delay option:
Position the jumper near the pushbutton:
— Front Door - 3 minute delay
— 2nd optional door - 1 minute delay
Position the jumper away from the pushbutton (default
position):
— Front Door - 15 second delay
— 2nd optional door - 1 minute delay
The receiver delay and the delay that is programmed in
the thermostat will be combined to provide an overall
delay.
MountingMounting the Receiver
The receiver can be mounted behind the thermostat in the
wall, inside the fan coil unit, or mounted on the wall.
Mounting screws or double-sided adhesive tape can be
used to mount the receiver.
Fig. 4. Receiver components.
Mounting the Door Sensor
1. Remove battery tab before installation. See Fig. 5.
Fig. 5. Battery tab removal.
2. Remove the plastic mounting bracket from the door
sensor housing.
3. Place the mounting bracket for the door sensor high
on the frame of the front door. Secure the bracket to
the door frame by using the two screws or adhesive
tape provided. See Fig. 6 on page 5.
M29150
TO THERMOSTAT
WIRING
HARNESS
RECEIVER
ANTENNA
1. WIRE RED AND WHITE WIRES TO
24 VAC POWER AND COMMON.
2. WIRE WHITE/BROWN AND
BROWN WIRES TO DRY CONTACT
TERMINALS ON THERMOSTAT.
M29151
TOP END VIEW
BOTTOM END VIEW
JUMPER PUSHBUTTON
WIRING
HARNESS
CONNECTOR
LED
PULL OUT
BEFORE USE
M29152