The POD 40c is 40 feet (12 m) long with 1100U of rack capacity and twenty-two 50U 19-inch (482 mm) deep racks (Figure 12). It offers capacity equivalent to a 5,000 ft2 (464 m2) traditional data center. It provides up to 600 kW of non-redundant capacity or 380 kW of fully redundant capacity. Facilities personnel can connect it directly into 480 V utility power and the chilled water system.

The POD 20c is 20 feet (6 m) long with 500U of rack capacity in ten 50U 19-inch (482 mm) deep racks. It offers capacity equivalent to a 2,000 ft2 (186 m2) traditional data center. It provides up to 290 kW of non-redundant power capacity or 145 kW of fully redundant capacity. Facilities personnel can connect it directly into 480 V utility power and the chilled water system.

Figure 12: The design of the HP POD 40c

We engineered the HP POD 40c and 20c for the highest efficiency of a water-cooled data center with standard air-cooled IT. The PODs minimize power losses by decreasing the number of power conversions. High-voltage 3-phase AC (400-480v AC depending upon location) is used as the input to the POD and then delivered directly to the racks as separate single-phase feeds for distribution to the servers. Highly efficient airflow and separate hot and cold aisles minimizes mixing and recirculation, and it maximizes cooling efficiency with a cold aisle that can be run up to 90°F (32°C).