D/G-04 Installation
Friction Losses
Calculating Friction Losses in Suction Piping
When following the above recommendations (under “inlet Piping”) for minimum hose/pipe I.D. and maximum length, frictional losses in the suction piping are negligible (i.e., Hf = 0) if you are pumping a
When pumping
In general, frictional losses increase with increasing viscosity, increasing
Consult the factory before pumping viscous fluids.
Minimizing Acceleration Head and Frictional Losses
To minimize the acceleration head and frictional losses:
•Keep inlet lines less than 3 ft (1 m) long
•Use at least 5/8 in. (16 mm) I.D. inlet hose
•Use soft hose
•Minimize fittings (elbows, valves, tees, etc.)
•Use a suction stabilizer on the inlet.
Net Positive Suction Head
NPSHa must be equal to or greater than NPSHr. If not, the pressure in the pump inlet will be lower than the vapor pressure of the fluid— and cavitation will occur.
Calculating the NPSHa
Use the following formula to calculate the NPSHa: NPSHa = Pt + Hz - Hf - Ha - Pvp
where:
Pt = Atmospheric pressure
Hz = Vertical distance from surface liquid to pump centerline (if liquid is below pump centerline, the Hz is negative)
Hf = Friction losses in suction piping
Ha = Acceleration head at pump suction
Pvp = Absolute vapor pressure of liquid at pumping temperature
NOTES:
•In good practice, NPSHa should be 2 ft greater than NPSHr
•All values must be expressed in feet of liquid
Atmospheric Pressure at Various Altitudes
Altitude | Pressure | Altitude | Pressure |
(ft) | (ft of H2O) | (ft) | (ft of H2O) |
0 | 33.9 | 1500 | 32.1 |
500 | 33.3 | 2000 | 31.5 |
1000 | 32.8 | 5000 | 28.2 |
Discharge Piping
NOTE: Consult the Factory before manifolding two or more pumps together.
NOTE:
Hose and Routing
Use the shortest,
Select pipe or hose with a working pressure rating of at least
1.5times the maximum system pressure. EXAMPLE: Select a
Use about 6 ft (1.8 m) of flexible hose between the pump and rigid piping.
Support the pump and piping independently.
Pressure Regulation
IInstall a pressure regulator or unloader in the discharge line. Bypass pressure must not exceed the pressure limit of the pump.
Size the regulator so that, when fully open, it will be large enough to relieve the full capacity of the pump without overpressurizing the system.
Locate the valve as close to the pump as possible and ahead of any other valves.
Adjust the pressure regulating valve to no more than 10% over the maximum working pressure of the system. Do not exceed the manufacturer’s pressure rating for the pump or regulator.
Route the bypass line to the supply tank, or to the suction line as far as possible from the pump (to reduce the chance of turbulence and cavitation).
If the pump may be run for a long time with the discharge closed and fluid bypassing, install a thermal protector in the bypass line (to prevent severe temperature buildup in the bypassed fluid).
CAUTION: Never install shutoff valves in the bypass line or between the pump and pressure regulator or relief valve.
Provide for permanent or temporary installation of a pressure gauge to monitor the discharge pressure at the pump.
For additional system protection, install a
7 |