AC Controls
Contactors —
General
|
|
|
|
|
|
|
| NEMA Size 1 |
| NEMA Size 3 |
| NEMA Size 5 |
|
|
|
|
|
|
|
|
Type 3TF
Key Features
JFully NEMA Rated Sizes
JDouble Break Contacts
JSilver Tin Oxide Contacts, Cadmium- Free (Sizes
JHigher Locked Rotor Current Ratings, Up to 840% (Sizes
JArc Chutes with Arc Splitters; Fast Arc
Quenching.
Table 15.27 Contactor Technical Data
JLowest Contact Bounce (2 Milliseconds or less on Most Sizes)
JTouch Safe Power Terminals (Sizes
JTouch Safe Control Terminals (Sizes
J
JVisual ON / OFF indicator
J
JFast Termination System — Wire Funnels, Wire Stops, Screwdriver Guide Holes, and Captive Hardware
JLong Mechanical Life
—15 Million (Size 00)
—10 Million (Size
—5 Million (Size
JUL Listed and CSA Certified
15
AC Controls
|
|
|
| NEMA Size |
|
|
|
|
|
|
|
| |
Measured Parameter |
|
| 00 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | |
Ampere Rating (Open) | Amps | 10 | 20 | 30 | 50 | 100 | 150 | 300 | 600 | 900 | 1350 | ||
Ampere Rating (Enclosed) | Amps | 9 | 18 | 27 | 45 | 90 | 135 | 270 | 540 | 810 | 1215 | ||
Maximum Voltage Rating | Volts | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | ||
Squirrel Cage |
| 200 V, 60 Hz |
| 1.5 | 3 | 7.5 | 10 | 25 | 40 | 75 | 150 | — | — |
Motor Maximum |
| 230 V, 60 Hz |
| 1.5 | 3 | 7.5 | 15 | 30 | 50 | 100 | 200 | 300 | 450 |
Horsepower |
| HP | |||||||||||
| 380 V, 50 Hz | 1.5 | 5 | 10 | 25 | 50 | 75 | 150 | 300 | — | — | ||
|
|
| |||||||||||
|
|
| 2 | 5 | 10 | 25 | 50 | 100 | 200 | 400 | 600 | 900 | |
Resistive |
| 120 VAC |
| — | — | 3 | 5 | 10 | 15 | 30 | 60 | 90 | a |
Heating |
| 240 VAC |
| — | — | 6 | 10 | 20 | 30 | 60 | 120 | 180 | a |
| kW | ||||||||||||
| 480 VAC |
| — | — | 12 | 20 | 40 | 60 | 120 | 240 | 360 | a | |
|
| 600 VAC |
| — | — | 15 | 25 | 50 | 75 | 150 | 300 | 450 | a |
Resistive |
| 120 VAC |
| — | — | 5 | 8.5 | 17 | 26 | 52 | 105 | 155 | a |
Heating |
| 240 VAC |
| — | — | 10 | 17 | 34 | 68 | 105 | 210 | 315 | a |
| kW | ||||||||||||
| 480 VAC | — | — | 20 | 34 | 68 | 105 | 210 | 415 | 625 |
| ||
|
| a | |||||||||||
|
| 600 VAC |
| — | — | 25 | 43 | 86 | 130 | 260 | 515 | 775 | a |
Capacitor |
| 240 VAC |
| — | — | — | 12 | 27 | 40 | 80 | 160 | 240 | 360 |
Switching |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 480 VAC | KVAR | — | — | — | 25 | 53 | 80 | 160 | 320 | 480 | 720 | |
| |||||||||||||
| 600 VAC |
| — | — | — | 31 | 67 | 100 | 200 | 400 | 600 | 900 | |
|
|
| |||||||||||
Transformer |
| 120 VAC |
| — | 0.6 | 1.2 | 2.1 | 4.1 | 6.8 | 14 | 27 | 41 | 61 |
Switching |
| 240 VAC |
| — | 1.2 | 2.4 | 4.1 | 8.1 | 14 | 27 | 54 | 81 | 122 |
| kVA | ||||||||||||
| 480 VAC | — | 2.4 | 4.9 | 8.3 | 16 | 27 | 54 | 108 | 162 | 244 | ||
|
| ||||||||||||
|
| 600 VAC |
| — | 3 | 6.2 | 10 | 20 | 34 | 68 | 135 | 203 | 304 |
Transformer |
| 208 VAC |
| — | 1.8 | 3.6 | 6.3 | 12 | 30 | 41 | 81 | 122 | 182 |
Switching |
| 240 VAC |
| — | 2.1 | 4.3 | 7.2 | 14 | 23 | 47 | 94 | 140 | 210 |
| kVA | ||||||||||||
| 480 VAC | — | 4.2 | 8.5 | 14 | 28 | 47 | 94 | 188 | 280 | 420 | ||
|
| ||||||||||||
|
| 600 VAC |
| — | 5.2 | 11 | 18 | 35 | 59 | 117 | 1350 | 351 | 525 |
AC Coil |
| Overall | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 60 | 60 | 60 |
Ratings |
| Inrush | VA | 68/87 | 101/32 | 101/32 | 183/233 | 330/410 | 910/1090 | 2450/2960 | 2900 | 4000 | 4200 |
|
| ||||||||||||
|
| Sealed | VA | 10/12 | 12.1/16.1 | 12.1/16.1 | 17/21 | 32/39 | 58/70 | 115/146 | 105 | 140 | 100 |
Operating |
| to 10% overvoltage, |
|
|
|
|
|
|
|
|
|
|
|
Times |
| (warm or cold coil) Total | MS | ||||||||||
(valid for 20% |
| Opening Time Includes | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
Undervoltage) |
| Arcing Time Closing Delay |
|
|
|
|
|
|
|
|
|
|
|
Operating |
|
| |||||||||||
Resistance To Shock (Rectangular pulse) | G/MS | 5.5/5 3.2/10 | 5.7/5 9/5 | 5.7/5 9/5 | 9.2/5 4.8/10 | 8.6/5 4.8/10 | 10.4/5 5.8/10 | 8.8/5 4.9/10 | — | — | — | ||
Conductor size/phase | AWG | (2) | (2) | (2) | (3) | (4) | |||||||
Auxiliary Contact Wire Size | AWG | (2) | (2) | (2) | (2) | (2) | (2) | (2) | (2) | (2) | (2) | ||
Mechanical Life (make/break operations) | MILL | 15 | 10 | 10 | 10 | 10 | 10 | 10 | 5 | 5 | 5 | ||
Total Auxiliary Contacts Available |
| 4 | 4 | 4 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | ||
Auxiliary Contact Rating A600/P600 |
| YES | YES | YES | YES | YES | YES | YES | YES | YES | YES |
aFor ratings contact Siemens.
298 | Siemens Electrical Products and Systems | CSI Section 16160 | |