HP Type F02 Description, Magnetic Latch Operation, Ballast Load, Combination Lighting Contactors

Models: Class MMS and MRS MMS and MRS Class SMF Type K02 Type F02

1 29
Download 29 pages 42.09 Kb
Page 13
Image 13

AC Controls

Manual Starters and Switches

General

 

 

Type CLM Magnetically-Latched, 30-400A

 

 

Description

 

 

AC lighting contactors provide a safe con-

 

 

venient means of local or remote switch-

 

 

ing of relatively large tungsten, fluores-

 

 

cent or mercury arc lamp loads.

 

 

Siemens AC lighting contactors are

 

 

designed to withstand the large initial

 

 

inrush currents of tungsten lamp loads

 

 

without the contacts welding. They are

 

 

fully rated contactors and do not require

 

 

any derating as do standard motor con-

 

 

trol contactors. They are UL Listed and

 

 

CSA Certified.

 

 

Magnetic Latch Operation

 

 

A permanent magnet is built into the con-

 

 

tactor structure of the 30,60,100, and

 

 

200 ampere contactors that will maintain

 

 

the contactor in its energized state indefi-

 

 

nitely without using control power. When

 

 

energized, a DC current is applied that

 

 

produces a magnetic field that reinforces

 

 

the polarity of the permanent magnet,

 

 

and the contactor pulls in immediately.

 

 

The current to the coil is disconnected by

 

 

the coil clearing interlock. In order to drop

 

 

out the contactor it is necessary to apply

 

 

a field through the OFF coil in the reverse

 

 

direction to the permanent magnet. This

 

 

momentarily cancels the magnetic attrac-

 

 

tion and the contactor drops out.

 

 

Cu / AI terminals are provided as stan-

 

 

dard except on 30 ampere devices which

 

 

are for copper wire only.

 

 

Ballast Load:

 

 

600 volts AC, breaking all lines. Tungsten

 

 

Lamp Loads, Max. Volts:

 

 

Line-to-Line, 480 AC

 

15

 

Line-to-Neutral, 277 AC

 

 

Combination Lighting Contactors

 

 

It is desirable to install the branch circuit

 

ControlsAC

protective device and lighting contactor,

 

combining switching and over-current

 

 

 

 

protection, in one enclosure.

 

 

 

Type CLM Magnetically-Latched, 20A Multi-Pole

Combination lighting contactors are well suited for industrial, highway and area lighting applications, or where a lighting circuit may have to be disconnected for periodic maintenance. They may also be used for resistance heating loads.

CLM Lighting Contactors

The CLM Lighting Contactors can be used with metal halide, mercury vapor, quartz halogen, tungsten, and fluorescent lighting. They provide reliable and conve- nient lighting control in numerous applica- tions, such as industrial plants, schools, hospitals, office buildings, shopping cen- ters, airports, stadiums, etc. The CLM’s are listed under UL 508 with no derating when used open or enclosed. Optional solid-state control modules are available to allow control of the CLM lighting con- tactors directly from energy management systems, microprocessors, photoelectric cells, timers, and similar control devices. They permit programmable time schedul- ing of loads, automatic control of lighting near windows to allow the use of natural ambient lighting levels, and manual over- ride of all lighting circuits from any num- ber of local control stations or from a central location. These optional modules are integrally mounted onto the base of the lighting contactor.

Table 15.23 20 Ampere CLM

Max. AC Voltage and Ampere Ratings

 

 

Poles to Load

 

Load

Amps

 

2 for 1-Phase

Type

Cont.

1 for 1-Phase

3 for 3-Phase

Tungsten

20

250V AC

Ballast

20

347V AC

600V AC

General

30

347V AC

600V AC

Max. DC Voltage and Ampere Ratings

Load

Amps

Poles to Load

 

Type

Cont.

2 in Series

3 in Series

General

20

125V DC

250V DC

Type CLM Electrically-Held (20-400A)

CLH Lighting Contactors

Class CLH electrically-held lighting con- tactors provide a safe convenient means of local or remote switching for tungsten and ballast lamp loads, mercury arc lamps, 3 phase resistive heating, 480 volts line to line, 277 volts line to neutral. Available in 20 ampere through 400 ampere sizes in NEMA Type 1, 3R / 12, 4 stainless steel, 4X non-metallic type enclosures and open type. The CLH con- tactors are available in 2–12 pole 20 ampere, 3–12 pole 30 and 60 ampere and 3 pole in 100–400 ampere sizes. UL Listed and CSA certified.

Table 15.24

CLH Lighting Contactors

3-Phase Tungsten

3-Phase Non-

 

and Ballast Lamp

Motor Loads

 

Loads

3-Phase Mercury

 

480V Line to Line

ARC Lamps

No.

277V Line to

3-Phase Resistive

of

Neutral

Heating

Poles

 

 

2, 3, 4,

20

20

6, 8, 10,

 

 

12

30

30

3, 6,

9 & 12

 

 

60

60

3, 6,

9 & 12

 

 

100

100

3

200

200

3

300

300

3

400

400

3

Combination Lighting and Heating Features:

JDisconnect Switch and Circuit Breaker Types

JRugged Flange Mounted Handle

JEasy Installation

JOccupies Less Space

JIncreased Operator Protection

JRoom To Spare for Modifications

JClass R Fuses Standard

JElectrically and Mechanically Held

J30–300 Amperes

JUL Listed

296

Siemens Electrical Products and Systems

CSI Section 16160

Specification Guide

 

 

Page 13
Image 13
HP Type F02 Description, Magnetic Latch Operation, Ballast Load, Combination Lighting Contactors, CLM Lighting Contactors