AC Controls
Manual Starters and Switches
General
|
| Type CLM |
|
| Description |
|
| AC lighting contactors provide a safe con- |
|
| venient means of local or remote switch- |
|
| ing of relatively large tungsten, fluores- |
|
| cent or mercury arc lamp loads. |
|
| Siemens AC lighting contactors are |
|
| designed to withstand the large initial |
|
| inrush currents of tungsten lamp loads |
|
| without the contacts welding. They are |
|
| fully rated contactors and do not require |
|
| any derating as do standard motor con- |
|
| trol contactors. They are UL Listed and |
|
| CSA Certified. |
|
| Magnetic Latch Operation |
|
| A permanent magnet is built into the con- |
|
| tactor structure of the 30,60,100, and |
|
| 200 ampere contactors that will maintain |
|
| the contactor in its energized state indefi- |
|
| nitely without using control power. When |
|
| energized, a DC current is applied that |
|
| produces a magnetic field that reinforces |
|
| the polarity of the permanent magnet, |
|
| and the contactor pulls in immediately. |
|
| The current to the coil is disconnected by |
|
| the coil clearing interlock. In order to drop |
|
| out the contactor it is necessary to apply |
|
| a field through the OFF coil in the reverse |
|
| direction to the permanent magnet. This |
|
| momentarily cancels the magnetic attrac- |
|
| tion and the contactor drops out. |
|
| Cu / AI terminals are provided as stan- |
|
| dard except on 30 ampere devices which |
|
| are for copper wire only. |
|
| Ballast Load: |
|
| 600 volts AC, breaking all lines. Tungsten |
|
| Lamp Loads, Max. Volts: |
|
| |
| 15 | |
| ||
|
| Combination Lighting Contactors |
|
| It is desirable to install the branch circuit |
| ControlsAC | protective device and lighting contactor, |
| combining switching and | |
|
| |
|
| protection, in one enclosure. |
|
|
|
Type CLM
Combination lighting contactors are well suited for industrial, highway and area lighting applications, or where a lighting circuit may have to be disconnected for periodic maintenance. They may also be used for resistance heating loads.
CLM Lighting Contactors
The CLM Lighting Contactors can be used with metal halide, mercury vapor, quartz halogen, tungsten, and fluorescent lighting. They provide reliable and conve- nient lighting control in numerous applica- tions, such as industrial plants, schools, hospitals, office buildings, shopping cen- ters, airports, stadiums, etc. The CLM’s are listed under UL 508 with no derating when used open or enclosed. Optional
Table 15.23 20 Ampere CLM
Max. AC Voltage and Ampere Ratings
|
| Poles to Load |
|
Load | Amps |
| 2 for |
Type | Cont. | 1 for | 3 for |
Tungsten | 20 | 250V AC | — |
Ballast | 20 | 347V AC | 600V AC |
General | 30 | 347V AC | 600V AC |
Max. DC Voltage and Ampere Ratings |
Load | Amps | Poles to Load |
|
Type | Cont. | 2 in Series | 3 in Series |
General | 20 | 125V DC | 250V DC |
Type CLM
CLH Lighting Contactors
Class CLH
Table 15.24
CLH Lighting Contactors
| |||
and Ballast Lamp | Motor Loads |
| |
Loads |
| ||
480V Line to Line | ARC Lamps | No. | |
277V Line to | of | ||
Neutral | Heating | Poles | |
|
| 2, 3, 4, | |
20 | 20 | 6, 8, 10, | |
|
| 12 | |
30 | 30 | 3, 6, | |
9 & 12 | |||
|
| ||
60 | 60 | 3, 6, | |
9 & 12 | |||
|
| ||
100 | 100 | 3 | |
200 | 200 | 3 | |
300 | 300 | 3 | |
400 | 400 | 3 |
Combination Lighting and Heating Features:
JDisconnect Switch and Circuit Breaker Types
JRugged Flange Mounted Handle
JEasy Installation
JOccupies Less Space
JIncreased Operator Protection
JRoom To Spare for Modifications
JClass R Fuses Standard
JElectrically and Mechanically Held
J
JUL Listed
296 | Siemens Electrical Products and Systems | CSI Section 16160 | |
Specification Guide | |||
|
|