Supported facility connections

Humidifier specifications

A dedicated supply of domestic water is required if the optional humidifier is installed. For exact requirements for the humidifier model that was installed, see the humidifier manual supplied with the HP POD.

Item

1

2

Component

Humidifier drain

Water supply

For more information about the humidifier, see the documentation developed by the humidifier manufacturer.

Convenience outlets

The HP POD is prewired for a convenience outlet on the inside of the unit. This circuit is not part of the power provided by the main switchboard feeding the 3-phase power to the HP POD. To energize this circuit, you must supply a dedicated single phase, 16-or 20-amp branch circuit from your facility at the appropriate voltage. Make sure that the branch circuit is connected to the prewired exterior mounted junction box and must be wired in accordance with local regulations and codes.

Grounding requirements

The neutrals and equipment grounding conductors for all 3-phase HP POD feeders must remain isolated. The two conductors can be bonded at the power source only.

Supported facility connections 19