Failover from Primary Cluster to Recovery Cluster

After reception of the Continentalclusters alert and alarm, the administrators at the recovery site follow the prescribed processes and recovery procedures to start the protected applications on the recovery cluster. Note that data corruption may occur in situation where a disaster occurs at the primary cluster while the data refresh from secondary disk array to the recovery disk array is in progress. Under these circumstances, the data in the recovery replication group devices in the recovery disk array is not usable. The data can be recovered by restoring an old copy of the data from the local mirror devices (device C’) in the recovery disk array; as shown in Figure 7.

Figure 7 – Failover from Primary Site to Recovery Cluster

Execute the following commands to restore the data:

1.If the data was being refreshed from the primary site to the recovery site, restore the data from the local mirror to the recovery replication group devices in the recovery disk array.

2.Check the data restore progress assuming step 1 applies.

3.Once the restore completed, split the local mirror device (device C’) from the recovery replication group. The data in the recovery disk array may not be current but should be consistent. There is no additional procedure needed. Metrocluster is programmed to handle this case.

4.After the application is up and running, re-establish the local mirror devices as mirrors of the standard devices for an additional copy of the data.

Failback from the Recovery Cluster to the Secondary Site within the Primary Cluster

This procedure is used when the application fails back and runs on the secondary site while the primary site is still down.

1.Halt the Continentalclusters monitor package.

2.Halt the Continentalclusters recovery packages at the recovery site.

3.Split the local mirror device (device C’) from the recovery replication group in the recovery disk array.