Hubbell Industrial Controls, Inc.
Electric Fire Pump Controllers
Specifications for LXi 2300 Controllers *
The fire pump controller shall be factory assembled, wired, and tested as a unit assembly, shall conform to the requirements of the latest editions of
The controller shall be of the combined manual/automatic type and be furnished in a floor mounted
All electrical components shall be accessible from the front for maintenance and service. No components or component wiring shall be permitted on the door of the enclosure. The controller shall have a common operating handle for both the line isolating switch and the controller circuit breaker mounted in the enclosure flange. The minimum withstand rating for the fire pump controller shall be 150,000 amps RMS symmetrical at
The controller shall have separate and independent pressure settings with minimum run timing capable of a setting of 10 minutes. Settings of the pressures shall be established at the time of the field acceptance test. Provisions shall be included to allow manual or automatic
The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, Power/Phase Failure, and one set of Form “C” contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory, Emergency Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor,
The controller shall be equipped with LXi intelligent fire pump control system logic. All firmware shall be
The digital pressure readings and settings shall be displayed on the LXi LCD mounted on the enclosure flange. The LCD screen shall be 4 x 20 (4 lines of 20 characters) per screen, and the screens may be scrolled to give a total of 320 characters. The real time display shall give simultaneous
The event alarm caches shall be compartmentalized, and no compartment shall
1.Events that have occurred during a pump idle period
2.Events that occurred during the last start period
3.Events that occurred during the last run period
4.Events that occurred during the last stop period.
The LED displays shall be mounted on the enclosure flange and have an LED for the following, with provisions for three spare LED’s to be available and programmable for other options or event displays.
Power Available | Fail to Start | Lockout On | Low Suction |
Phase Reversal | Run Timer On | Pump Start Delay On | Shorted SCR |
Pump Running | Locked Rotor | Overload | Overtemp SCR |
Pressure Switch Start | Local Manual Start | Remote Start | Emergency Manual Start |
Local Manual Stop | Start Timer/Accelerate |
|
|
The LED displays shall be mounted on the enclosure flange and have an LED for the following:
Programming of the LXi logic shall be from the touch pad mounted on the enclosure flange. Programming shall be password protected so that only authorized personnel can change the logic functions. The fire pump controller shall be Model LXi 2300 equipped with LXi Logic as manufactured by Hubbell Industrial Controls, Inc.