Hunter Fan installation instructions 44127, 44132 Programmable Thermostat, Labeling Your Wires

Models: 44127 44132

1 2
Download 2 pages 42.07 Kb
Page 1
Image 1
44127, 44132 Programmable Thermostat

1

 

44127, 44132 Programmable Thermostat

Installation Sheet

 

Preparation

1

Gathering Tools and Warnings

 

This thermostat is compatible with most conventional oil, gas, electric, hot water systems, single stage, and multi-stage heat pumps. This thermostat will not control line voltage systems.

You will need the following tools to complete your installation: • Phillips Screwdriver (#2)

• Two 1.5V (AA) size alkaline batteries

Take note of these warnings and cautions before proceeding:

• Read all installation instructions before beginning installation! If you still need assistance after reading this manual, call our Technical Support at 1-888-830-1326.

• Do not disconnect the wires from your old thermostat until all wires have been properly labeled. You must label all wires properly because wire color may not indicate the function of the wire.

• All wiring must be done in accordance with local code and ordinances.

• Always turn power off to your furnace/compressor before the installation process. Failure to do so could result in damage to your thermostat and/or your heating and cooling system. Do not restore power until your installation is complete.

• This thermostat is designed for use with 24V AC/millivolt systems with a maximum of 1 amp. Higher amp or line voltage systems will cause damage to your system and increase the risk of fire.

Conventional

RH

 

RH

 

 

 

 

 

 

RC, R

 

RC

 

 

 

 

 

 

Y, Y1

 

Y

 

 

 

 

 

 

G, F

 

G

 

 

 

 

 

 

W, W1

 

W

 

 

 

 

 

 

W2

 

W2

 

 

 

 

 

 

Y2

 

Y2

 

 

 

 

 

 

C

 

C

 

 

 

 

 

 

A

 

A

 

 

 

 

Figure 3a.

Heat Pump

R, V

 

R

 

 

 

 

 

 

Y, Y1, M

 

Y

 

 

 

 

 

 

G, F

 

G

 

 

 

 

 

 

L, F, X

 

L

 

 

 

 

 

 

O, R

 

O

 

 

 

 

 

 

B

 

B

 

 

 

 

 

 

W2, E, X,

 

E

Aux

 

 

Y2

 

Y2

 

 

 

 

 

 

C, X, X1, B

 

C

 

 

 

Figure 3b.

After writing down the wire colors and letters, use the terminal stickers to label the wires. Figures 3a and 3b will help you depending on system type; Conventional or Heat Pump. Not all terminals will be used, this will be determined by your system type.

To ensure wires do not fall back into the wall hole, you may tape them to the wall, or wrap them around a pencil.

Figure 4. may assist you if your old thermostat is a heat pump from one of the listed Manufacturers and your wire labels do not match. It is located on the back of this sheet. These tips will also help you in wiring:

• Only 1 reversing valve is needed to run a heat pump. If both “O” and “B” are present, “B” may be a common wire.

• Often, 2-wire heat only systems do not have terminal labels. Connect 1 wire to the Rh terminal and the other to W.

• If you have a 3-wire hot water system, the damper valve control wire will be labeled and attached to the “A” terminal.

• If you need further assistance with wiring, or determining your system type, you can contact our Technical Support Department. See the “Technical Support” section for information.

4.  Check the charts on the back of this sheet and identify your system type. They are divided by Conventional and Heat Pump installations.

5.  Raise all of the levers on the terminals you will be using. Heat Pump Installation labels are located on the left of the terminal blocks on the mounting plate and Conventional labels are on the right. If your installation does not call for the jumper, remove it now. It is located underneath the wire holes, between the RH and RC terminals on the conventional side. Figure 9.

6.  If one of the terminals you need has a tab in front of it, use your finger to break the tab away. Figure 9.

Note: Only break tabs you know you will be using. Double check your wiring configuration and make sure you are familiar with the terminals you will be using.

Levers

Jumper

RH

RH

W

 

 

 

RC

 

 

Y

 

Insert

 

Wires

 

 

G

 

 

W

 

 

Tabs

 

Figure 9.

7.  Insert the bare end of each wire all the way into the appropriate hole in the terminal block that matches the wire label then lower the lever. This will lock each of the wires in place. Tuck excess wire back into wall after they have been locked in the mounting plate.

Note: Do not insert the wires into the holes in the top of the

Old Thermostat Removal

1.  Turn off power to your compressor and furnace.

2.  Remove the cover to your existing thermostat. Some thermostats may have screws or other locking devices that must first be removed. Once the wallplate is exposed, locate the wire terminals and try to identify the wire designations. If the wire terminals are not visible, they may be connected to the back of the wallplate. Look for any additional screws, tabs, or locking devices to remove the wallplate. See Figure 1. If you are still unable to find the terminals for the wires, it may be necessary to contact the manufacturer of the original thermostat.

RC Y G

W

 

 

 

 

 

 

 

Wallplate

Thermostat

Cover

 

Y G

W

 

 

 

RC

 

 

 

Wallplate

Thermostat

Cover

 

 

 

Figure 1.

 

Labeling Your Wires

Use the table in Figure 2. to write down your wire colors and the letter designations on the old thermostat. This will allow you to keep a record of your old thermostat’s wiring configuration should you need to refer to it at a later time. This will also help our Technical Support Department determine your system type and proper wiring, should you need to contact them. Wire color does not indicate the function of the wire, this is being used only to help determine which wire has what letter designation.

Wire Color

Wire letter

Figure 2.

Installation

2

Mounting the Wallplate

 

1.  Remove the mounting plate by pulling it straight off the back of the Thermostat. Figure 5.

Figure 5.

2.  Pull the wires through the back of the mounting plate, ensuring none of the wire labels are removed. Figure 6.

 

C

 

Y

W

G

RH

Figure 6.

3.  Using a Phillips Screwdriver, Partially install 1 screw into the top hole of the thermostat. Ensure the thermostat is level using the bubble level on the mounting plate Figure 7., then install the other screw. Tighten both screws until secure. Figure 8.

bubble level

Figure 7.

RHInstallation Sheet

W

Y

C

G

Figure 8.

mounting block. The wires should be inserted into the front close to the hole in the mounting plate. See Figure 8.

8.  Before mounting the thermostat onto the mounting plate, turn it over and find the 2 switches located on the circuit board next to the battery compartment.

9.  Set the system switch to “Conv” if you have a conventional HVAC system or “HP” if you have a heat pump system. Set the furnace type to “Elc” if you have an electric convention system or a heat pump. “Gas/Oil” will be used if you have gas or oil based conventional system. Figure 10.

Note: Conventional systems use the compressor for air conditioning and a separate furnace for heat. Heat pump systems use the compressor for both heating and cooling.

Gas

Oil

HP

Elc

Conv

H.P.

Cnv.Gas

Elec

Figure 10.

10.  Lay the ribbon across the battery compartment and install 2

(AA)Batteries into the back of the thermostat over it, Figure 10., and snap the thermostat on to the mounting plate. Refer to “Setup” on page 10 of your owner’s manual to continue setup, scheduling, and daily use.

Figure 11.

Technical Support

If you have any additional questions or problems with your Hunter thermostat, please call:

USA: 1-888-830-1326

Canada: 1-866-268-1936

Hours of operation are from 7:00 am to 7:00 pm Monday - Friday and 8:00 am to 5:00 pm on Saturday, Central Time. You may also contact us over the Internet at www.hunterfan.com.

©2010 Hunter Fan Company

44066-01 R20100524

 

 

Page 1
Image 1
Hunter Fan installation instructions 44127, 44132 Programmable Thermostat, Gathering Tools and Warnings, Preparation