IBM 1500VA, 1000VA manual Standards, Operating environment, Hardware requirements

Models: 1500VA 1000VA

1 20
Download 20 pages 62.49 Kb
Page 7
Image 7
Standards

Electrical specifications

UPS 1,000 VA / 750W Tower - (single phase)

53961AX 1000 VA, 120V AC, 60 Hz, 8.8 A

Output through 8 NEMA 5-15R receptacles

53961JX 1000 VA, 100V AC, 60 Hz, 10.5 A

Output through 8 NEMA 5-15R receptacles

UPS 1,000 VA / 750 W Tower - (single phase)

53961KX 1,000 VA, 220-240V AC, 50 Hz, 4.6 A

Output through 8 IEC 320 C13 receptacles

UPS 1,500 VA / 1000 W Tower - (single phase)

53962AX 1440 VA, 120V AC, 60 Hz, 12.6 A

Output through 8 NEMA 5-15R, receptacles

UPS 1,500 VA / 1000 W Tower - (single phase)

53962JX 1200 VA, 100V AC, 60 Hz, 12.6 A

Output through 8 NEMA 5-20R, receptacles

UPS 1,500 VA / 1000 W Tower - (single phase)

53962KX 1,500 VA, 220-240V AC, 50 Hz, 6.9 A

Output through 8 IEC 320 C13 receptacles

Audible noise at 1 meter: 55 dBa (100% load)

Online thermal dissipation:

1AX, 1JX, 1KX - 853 BTU/hr

2AX, 2JX, 2KX - 1708 BTU/hr

Equipment approvals and safety

FCC

UL

CSA or cUL

CE Mark

NOM

GOST

BSMI Taiwan

CB Report

VCCI

C-Tick (Australia)

Korea KC

Standards

None

Operating environment

Temperature: 0° to 40.0° C (32° to 104° F) at 0 to 3,000 m (0 to 9,843 ft)

Relative humidity: 5% to 95%

Maximum altitude: 3,000 m (9,843 ft)

Hardware requirements

None

IBM United States Hardware Announcement 110-210

IBM is a registered trademark of International Business Machines Corporation 7