Physical and electrical specifications

Dimensions and weight:

Height: 85 mm (3.36 in)

Width: 443 mm (17.5 in)

Depth: 698 mm (27.5 in)

Weight:

Minimum configuration: 21.1 kg (46.5 lb)

Maximum configuration: 29.6 kg (65 lb)

Supported environment:

Air temperature

Server on: 10 to 35° C (50 to 95° F); altitude: 0 to 914 m (3,000 ft). Decrease system temperature by 0.75° C for every 1,000-foot increase in altitude.

Server off: 5 to 45° C (41 to 113° F)

Shipment: -40 to +60° C (-40 to 140° F)

Humidity

Server on: 20 to 80%; maximum dew point 21° C; maximum rate of change 5° C/hr

Server off: 8 to 80%; maximum dew point 27° C

Electrical

Models with 675 W power supplies:

100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 7.8 A

200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 3.8 A

Input kilovolt-amperes (kVA) (approximately):

Minimum configuration: 0.12 kVA

Maximum configuration: 0.78 kVA

Models with 460 W power supplies:

100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 5.3 A

200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 2.6 A

Input kilovolt-amperes (kVA) (approximately):

Minimum configuration: 0.12 kVA

Maximum configuration: 0.53 kVA

BTU output

Minimum configuration: 307 Btu/hr (90 watts)

Maximum configuration: 2260 Btu/hr (780 watts)

Noise level

6.5 bels (operating)

6.3 bels (idle)

IBM System x3650 M3