LIMITATIONS
The unit should be installed in accordance with all National, State and Local Safety Codes and the limitations listed below:
1.Limitations for the indoor unit, coil, and appropriate accessories must also be observed.
2.The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.
3.The maximum and minimum conditions for operation must be observed to ensure a system that will give maximum performance with minimum service.
TABLE 1: Application Limitations
Ambient Air Temperature | Air Temperature on | ||
on Outdoor Coil | Indoor Coil | ||
|
|
|
|
Min. DB | Max. DB | Min. WB | Max. WB |
50°F | 115°F | 57°F | 72°F |
4.The unit should not be operated at outdoor temperatures below 50°F without an approved low ambient operation accessory kit installed.
5.The maximum allowable line length for this product is 75 feet.
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the condenser coil, air discharge, and service access. See Figure 1.
NOTICE
For multiple unit installations, units must be spaced a minimum of 18” (46 cm) apart (coil face to coil face).
If the unit is to be installed on a hot sun exposed roof or a
Provide an adequate structural support.
ADD-ON REPLACEMENT/RETROFIT
When this unit is being used as a replacement for an
1.
2.
3.If
•Inspect the line set for kinks, sharp bends, or other restrictions, and for corrosion.
•Determine if there are any low spots which might be serving as oil traps.
•Flush the line set with a commercially available flush kit to remove as much of the existing oil and contaminants as possible.
•Install a suction line
4.If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina
| MINIMUM 18” SERVICE |
| |
60” OVERHEAD | ACCESS CLEARANCE | THERMOSTAT | |
ON ONE SIDE | |||
CLEARANCE |
| ||
|
| ||
| WEATHERPROOF |
| |
| DISCONNECT |
| |
| SWITCH |
| |
|
| NEC CLASS 1 WIRING | |
6” CLEARANCE |
| TO FURNACE OR | |
AROUND PERIMETER |
| AIR HANDLER | |
|
| TERMINAL BLOCK | |
|
| NEC CLASS 2 WIRING | |
|
| TO INDOOR COIL | |
NOTE: |
|
| |
ALL OUTDOOR WIRING | CONTROL |
| |
MUST BE WEATHERPROOF. |
| ||
ACCESS | SEAL OPENING(S) WITH | ||
| |||
| PANEL | PERMAGUM OR EQUIVALENT |
FIGURE 1: Typical Installation