For mobile home installation, select locations carefully to avoid thermal barriers that may form at the ceiling. For more details, see MOBILE HOME INSTALLATION below.

When mounting an alarm on the ceiling, locate it at a minimum of 4” (10 cm) from the side wall (see FIGURE 1).

When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a mini- mum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see FIGURE 1).

Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or room is more than 30 feet (9.1 m) long.

Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft (0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke alarms in rooms with ceiling slopes greater than 1 foot in 8 feet (.3m in 2.4 m) horizontally shall be located on the high side of the room.” NFPA 72 states: “A row of detectors shall be spaced and located within 3 ft (0.9m) of the peak of the ceil- ing measured horizontally” (see FIGURE 3).

4"

(10 cm)

CEILINGMINIMUM

DEAD AIR

SPACE

4"

(10 cm)

MINIMUM

BEST NEVER

HERE HERE

12"

(30.5 cm)

MAXIMUM

ACCEPTABLE

HERE

SIDE

WALL

FIGURE 1

 

NOT

 

IN THIS

 

AREA

4"

ANYWHERE

(102 mm)

IN THIS

 

AREA

3'

3'

(0.9 m)

(0.9 m)

 

NOT

 

IN THIS

SINGLE FLOOR PLAN

BEDROOM KITCHEN

BEDROOM BEDROOM

LIVING ROOM

BEDROOM

Smoke Alarms for Minimum Protection

Smoke Alarms for Additional Protection

Ionization Type Smoke Alarms with HUSH® Control or Photoelectric Type

MULTIPLE

FLOOR PLAN

BEDROOM HALL BEDROOM

LIVING

KITCHEN

ROOM

 

BASEMENT

 

ANYWHERE

AREA

IN THIS

 

AREA

4"

(102 mm)

3'

(0.9 m)

FIGURE 2

FIGURE 3

MOBILE HOME INSTALLATION

Modern mobile homes have been designed and built to be energy efficient. Install smoke alarms as recommended above (refer to RECOMMENDED LOCATIONS and FIGURES 1 and 2).

In mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. In such units, install the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see FIGURE 1).

If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall. For minimum protection, install at least one alarm close to the bedrooms. For additional protection, see SINGLE FLOOR PLAN in FIGURE 2.