120VAC Ionization Smoke Alarm
Architectural and Engineering Specifications
The smoke alarm shall be Kidde Model 1276E or approved equal. It shall be powered by a 120VAC, 60Hz source along with a 9V battery backup. The unit shall incorporate an ionization sensor with nominal sensitivity of 0.99%/ft. The temperature operating range shall be between 40°F and 100°F (4°C and 38°C) and the humidity operating range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a
The alarm shall include an easy access battery compartment that is opened and closed by pressing on the battery door. The 9V battery carrier will ensure proper battery backup protection by not allowing the battery door to close if the battery is placed in the unit incorrectly or if a battery is not present. The unit shall also provide an optional tamper resistant switch that will prevent the battery door from being opened.
The unit shall include a piezoelectric horn that is rated at 85 decibels at 10 feet. The unit shall include the Hush feature that silences the unit for approximately 7 minutes if a nuisance condition occurs. The alarm will chirp every 30 - 40 seconds while in hush mode and will automatically reset.
The unit shall incorporate 2 LED’s. A green LED will be constantly “ON” when AC power is present and will flash until reset (alarm memory) to indi- cate which alarm was the originating alarm at the last incident. Pressing the test button will reset the alarm memory condition. A red LED will flash once every
The unit shall at a minimum meet the requirements of UL217, NFPA72, and (chapter 11 2002 edition) The State of California Fire Marshall, NFPA101 (0ne and two family dwellings), Federal Housing Authority (FHA), Housing and Urban Development (HUD).
Unit Number 1276E
Installation of Smoke Alarm
The smoke alarm should be installed to comply with all local codes having jurisdic- tion in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous
FUSE OR CIRCUIT BREAKER
L
N
BLACK | RED |
WHITE |
|
First | Additional |
Alarm | Alarms |
Technical Specifications | |
Unit Number: | 1276E |
UPC: | |
Power Source: | 120VAC, 60HZ, 9V battery backup |
Audio Alarm: | 85dB at 10ft |
Temperature Range: | 40˚F to 100˚F (4˚C to38˚C) |
Humidity Range: | |
Sensor: | Ionization |
Size: | 5” in diameter x 1.75” depth |
Weight: | .75lbs |
Interconnects: | Up to 24 Kidde devices |
LED: | Green, normal operation |
| Red, alarm condition |
Warranty: | 5 year limited warranty |
Ordering Information
Gift Box UPC:
Part | Battery |
|
| Dimensions |
| Case/ | Layers/ | Skid |
Number | Type | I 2 of 5 | Pack Quantity | (w x d x h inches) | Weight | Skid | Skid | Weight |
|
|
|
|
|
|
|
|
|
1276E** |
| N/A | Individual | 5.62 x 1.875 x 5.62 | .75lbs | N/A | N/A | N/A |
|
|
|
|
|
|
|
|
|
Standard 9V | 307 84908 00135 2 | Master Pack (12 units) | 12 x 12 x 6.25 | 9lbs | 128 | 8 | 1558lbs | |
|
|
|
|
|
|
|
|
|
Standard 9V | 407 84908 00135 9 | Bulk Pack (36 units) | 19.5 x 12 x 12 | 27.2lbs | 24 | 4 | 652.8lbs | |
|
|
|
|
|
|
|
|
|
Standard 9V | 507 84908 00135 6 | Cut Case (36 units) | 12 x 17.5 x 12 | 27.2lbs | 24 | 3 | 652.8lbs | |
|
|
|
|
|
|
|
|
|
Alkaline 9V | 300 47871 27695 1 | Master Pack (12 units) | 12 x 12 x 6.25 | 9lbs | 72 | 4 | 648lbs | |
|
|
|
|
|
|
|
|
|
**Not for sale by individual unit