Kidde HD135F Architectural and Engineering Specifications, Technical Specifications, Gift Box UPC

Models: HD135F

1 2
Download 2 pages 61.4 Kb
Page 2
Image 2
Architectural and Engineering Specifications

120VAC Wire In with 9V Battery Back Up Heat Detector

Architectural and Engineering Specifications

The heat detector shall be Kidde Unit HD135F or approved equal. It shall be powered by a 120VAC, 60Hz source along with a 9V battery backup. The temperature operation range shall be between 40°F and 100°F (4°C and 38°C) and the humidity operation range shall be 5% - 95% relative humidity.

The heat detector can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a plug-in connector. A maximum of 24 Kidde devices can be interconnected in a multiple station arrangement. The inte connect system must not exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices (Smoke, heat, CO, etc) interconnected, it is still possible to intercon- nect 6 strobe lights and or relay modules. The alarm shall provide optional tamper resistance that deters removal of the unit from the wall or ceiling.

The unit shall include a piezoelectric horn that is rated at 85dB at 10ft. The unit shall incorporate a LED. A red LED will be constantly “ON” when AC power is present and will flash once approximately every 30-40 seconds to indicate that the smoke alarm is operating properly and will flash rapidly when the unit is alarming and will remain so until the air is cleared.

The unit shall incorporate a test button. The test button shall test all the electronic circuitry, horn, and battery.

The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter 10 & 11 2002 edition) The State of California Fire Marshall, NFPA101 (One and two family dwellings, Federal Housing Authority (FHA), Housing and Urban Development (HUD).

Unit Number HD135F

Technical Specifications

Unit Number:

HD135F

UPC:

0-25417-84135-0

 

 

Power Source:

120VAC, 60HZ, 9V battery backup

 

 

Sensor:

Heat

 

 

Audio Alarm:

85dB at 10ft

 

 

Temperature Range:

40˚F to 100˚F (4˚C to 38˚C)

 

 

Humidity Range:

5%-95% relative humidity (RH)

 

 

Size:

5” in diameter x 2” depth

 

 

Weight:

.75lbs

Interconnects:

Up to 24 Kidde devices

 

 

LED:

Red, AC power present,

 

alarm mode

 

 

Warranty:

5 year limited warranty

 

 

Installation of Heat Detector

The heat detector should be installed to comply with all local codes having jurisdiction in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in the interconnect system.

5"

2"

Ordering Information

Gift Box UPC:

0-25417-84135-0

 

 

 

 

 

 

Part

 

 

Dimensions

 

Case/

Layers/

Skid

Number

I 2 of 5

Pack Quantity

(w x d x h inches)

Weight

Skid

Skid

Weight

 

 

 

 

 

 

 

 

HD135F

N/A

Individual

4.75 x 2.45 x 5.65

.75lbs

N/A

N/A

N/A

 

 

 

 

 

 

 

 

HD135F

200 25417 84135 4

Master Pack (6 units)

6.5 x 10.5 x 6.5

4.5lbs

60

5

270lbs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

6

 

 

 

 

 

 

UNIT

MASTER PACK

Distributed by:

1394 South Third Street, Mebane NC 27302

1-800-880-6788 • www.kiddeus.com

Page 2
Image 2
Kidde HD135F warranty Architectural and Engineering Specifications, Technical Specifications, Installation of Heat Detector