120V AC/DC | Part Number 21006378 |
Battery Backup | Model i12040 |
| |
|
|
Architectural and Engineering |
| Installation of Smoke Alarm | ||||||||||||||||||||||||
Specifications |
| The smoke alarm must be installed to comply with all local codes having jurisdiction | ||||||||||||||||||||||||
| in your area. All wiring shall be in accordance with articles 210 and 300.3(B) of | |||||||||||||||||||||||||
The smoke alarm shall be Kidde model i12040 or approved equal. It shall be |
| the US National Electrical Code, ANSI / NFPA 70 and NFPA 72. The multiple station | ||||||||||||||||||||||||
| interconnect wiring must be in the same raceway as the AC power wiring. In addi- | |||||||||||||||||||||||||
powered by a 120VAC, 60Hz source along with a 9V battery backup. The |
| |||||||||||||||||||||||||
| tion the resistance if the interconnect wiring shall be a maximum of 10 ohms. | |||||||||||||||||||||||||
unit shall incorporate an ionization sensor with nominal sensitivity of .50 to |
| |||||||||||||||||||||||||
| Make certain all alarms are wired to a single, continuous | |||||||||||||||||||||||||
.98%ft. The temperature operation range shall be between 40˚F and 100˚F |
| line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. | ||||||||||||||||||||||||
(4˚C and 38˚C) and the humidity operating range shall be 5% - 95% relative |
| of wire can be used in the interconnect system. Use standard UL listed household | ||||||||||||||||||||||||
humidity. |
| wire as required by code. | FUSE OR CIRCUIT BREAKER |
|
|
|
|
|
|
|
|
| ||||||||||||||
The smoke alarm can be installed on any standard single gang electrical |
|
|
|
|
| L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| N |
|
|
|
|
|
|
|
|
| ||||||||||||
box, up to a 4” octagon junction box. The electrical connection (to the alarm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
shall be made with a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
be interconnected in a multiple station arrangement. The interconnect system |
|
|
|
|
|
| BLACK |
|
|
|
|
| RED | |||||||||||||
|
|
|
|
|
|
|
| WHITE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
must not exceed the NFPA (National Fire Protection Association) limit of 18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
initiation devices, of which 12 can be smoke alarms. With 18 initiating devic- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
es (smoke, heat, CO, etc.), interconnected, it is still possible to interconnect |
|
|
|
|
|
| First |
| Additional | |||||||||||||||||
6 strobe lights and or relay modules. The unit shall provide optional tamper |
|
|
|
|
|
| Alarm |
| Alarms | |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
resistance that deters removal of the unit from the wall or ceiling. |
| Technical Specifications | ||||||||||||||||||||||||
The alarm shall include a test button that will electronically simulate the |
| |||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
presence of smoke and cause the unit to go into alarm. This sequence tests |
| Model Number: | i12040 |
|
|
|
|
|
|
|
|
| ||||||||||||||
the unit’s electronics, battery and horn to ensure proper operation. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| UPC: |
|
|
|
|
|
|
| ||||||||||||||||||
The unit shall include a piezoelectric horn that is rated at 85 decibels at |
|
|
|
|
|
|
|
| ||||||||||||||||||
| Power Source: | 120VAC (80mA) with 9V Battery Back Up | ||||||||||||||||||||||||
10 feet. The unit shall include Smart HushTM feature that silences the unit for |
| |||||||||||||||||||||||||
approximately 7 minutes if a nuisance condition occurs. The unit shall also |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Sensor: | Ionization |
|
|
|
|
|
|
|
|
| |||||||||||||||
include a low battery warning utilizing a brief alarm chirp every |
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
onds for a minimum of seven (7) days. |
| Audio Alarm: | 85dB at 10ft |
| ||||||||||||||||||||||
The unit shall incorporate red and green LED indicators. The green LED |
| Temperature Range: | 40˚F (4.4˚C) to 100˚F (37.8˚C) | |||||||||||||||||||||||
(when illuminated) indicates the presence of AC power. The red LED (located |
| |||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
under the TEST/Hush button) has four modes of operation: |
| Humidity Range: |
| |||||||||||||||||||||||
Standby Condition: The red LED will flash every |
| Size: | 5.6” in diameter x 1.55” depth | |||||||||||||||||||||||
that the smoke alarm is operating properly. Alarm Condition: When the |
| |||||||||||||||||||||||||
| Weight: | .5lb |
|
|
|
|
|
|
|
|
| |||||||||||||||
alarm senses products of combustion and goes into alarm the red LED will |
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
flash one flash per second. The flashing LED and pulsating alarm will continue |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Interconnects: | Up to 24 Kidde devices | ||||||||||||||||||||||||
until the air is cleared. When units are interconnected, only the red LED of |
| |||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
the alarm that senses the smoke or is being tested (the originating unit) will |
| Wiring: | ||||||||||||||||||||||||
flash. All other units in the interconnected system will sound an alarm but |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LED: | Red, 4 modes of operation | ||||||||||||||||||||||||
their red LED’s will NOT flash. Alarm Memory: This smoke alarm is equipped |
| |||||||||||||||||||||||||
with an alarm memory, which provides a visual indication when an alarm has |
|
|
|
|
| Green, indicates AC power | ||||||||||||||||||||
been activated. The red LED will illuminate for about 1.5 seconds every 16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Warranty: | 10 year limited | ||||||||||||||||||||||||
seconds to indicate the memory condition. Smart HushTM Mode: The red LED |
| |||||||||||||||||||||||||
will illuminate for 1.5 seconds every 8 seconds, indicating the smoke alarm is |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
in the Smart HushTM Mode. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The unit shall at a minimum meet the requirements of UL217, NFPA72, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
(chapter 11), The State of California Fire Marshall, NFPA 101 (One and |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
two family dwellings) Federal Housing Authority (FHA), Housing and Urban |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Development (HUD). It shall also include a |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ordering Information
Ordering |
|
|
|
| Dimensions |
| Case/ | Layers/ | Skid |
Number | UPC |
| I2F5 | Pack Quantity | (w x d x h inches) | Weight | Skid | Skid | Weight |
N/A | N/A | individual* | 5.75 x 1.5 x 5.75 | 0.5 lbs | N/A | N/A | N/A | ||
21006378 | Cut Case (6 units) | 6.5 x 13.25 x 6 | 3 lbs | 147 | 7 | 441 lbs | |||
|
|
|
|
|
|
|
|
| |
21006373 | Bulk Pack (6 units) | 6 x 10.5 x 6 | 3 lbs | 147 | 7 | 441 lbs | |||
|
|
|
|
|
|
|
|
| |
21006930 | Display Pallet (36 units) | 20 x 24 x 40 | 20lbs | 4 | 1 | 90 lbs | |||
|
|
|
|
|
|
|
|
| |
Alk. Btry 21006928 | Cut Case (6 units) | 6.5 x 13.25 x 6 | 3 lbs | 147 | 7 | 441 lbs | |||
|
|
|
|
|
|
|
|
| |
Lith. Btry 21006929 | Cut Case (6 units) | 6.5 x 13.25 x 6 | 3 lbs | 147 | 7 | 441 lbs | |||
|
|
|
|
|
|
|
|
| |
21006375** | Cut Case (6 units) | 6.5 x 13.25 x 6 | 3 lbs | 147 | 7 | 441 lbs | |||
|
|
|
|
|
|
|
| ||
21006372** | Cut Case (3 Twin Packs) | 6.5 x 13.25 x 6 | 3 lbs | 147 | 7 | 441 lbs | |||
|
|
|
|
|
|
|
| ||
*Not for sale by individual unit | **Includes Wiring Adapters |
|
|
|
|
|
|